High-voltage (HV) infrastructure mamawhna hmunah chuan Voltage Transformers (VT) leh Capacitive Voltage Transformers (CVT) ang instrument te 400kV-a dik leh insulation integrity finfiah hi mission pawimawh tak a ni. Tunhma chuan heng level-a test-na atan hian laboratory hmanrua lian tak tak, stationary tak tak a ngai thin.
Mahse, Series Resonance technology hmasawn tak avangin 400kV testing chu lab atanga field-ah a kal ta a ni. Hetah hian next-generation 400kV / 1A AC Resonant Test System-a technical mamawh leh hman dan tur thuk tak kan rawn tarlang dawn a ni.
1. Technical Specifications te chu a hmasa berah
Global utility standard (IEC 61869 ang chi) zawm tur chuan field test set chuan extreme output power leh input accessibility balance a ngai a ni.
Input Voltage: 230 V AC, 50 Hz (Single Phase) a ni a, a chhuahna tur hmun leh a hmanna tur hmun a awm lo.Standard site power emaw portable generator emaw atanga hmuh theih.
A chhuahna Voltage: 400 kV AC, 50 Hz – 1000 a ni.EHV (Extra High Voltage) transmission assets te enkawl thei.
Output Current: 1 A – 1000 a ni.Test theihna zawng zawng 400 kVA pe thei.
Waveform: Sinusoidal thianghlim (THD < 1%) – 1000 a ni.Metrology leh calibration dikna atan a pawimawh hle.
2. The Core Technology: 230V hian 400kV a siam chhuah dan
He system portability thuruk chu Series Resonance Principle a ni.
System-a reactor-a inductance (LL) chu test object (VT emaw CVT emaw) capacitance (CC) nen a inmil chuan system chu 50 Hz-ah resonance state-ah a lut a ni.
Q-Factor Advantage: Resonant state-ah chuan system chuan voltage chu factor 30 atanga 80 (Quality Factor) thlengin a "amplify" thin.
Efficiency: Power supply hian "loss" energy chauh a pe a ngai a ni. Hei hian 230V single-phase input chuan 400kV output lian tak a khalh thei a, hei hian-site-a heavy-duty industrial power grids hman a ngai tawh lo.
3. Hlutna sang tak-Value Applications
A. Capacitive Voltage Transformers (CVT) hmanga siam chhuah dan (calibration) a ni
CVT hi 400kV grids-a revenue metering leh venhimna kawngkhar bulpui ber a ni. Capacitive an nih avangin resonant testing atan pawh candidate tha tak an ni. Kan system hian "brute-force" transformer-a hman tlanglawn interference awm lovin CVT-te ratio leh phase error calibrate-na atana mamawh stability leh frequency precision a pe a ni.
B. Gas-Insulated Switchgear (GIS/GSS) VT Testing hmanga thil tih a ni
GIS environment chhunga VT test nan hian hmun remchang a awm avangin compact solution a ngai a ni. Kan Resonant Reactors modular design hian positioning flexible tak a siam a, khawpui substation tight takah pawh GIS VT-ah AC withstand leh accuracy test neih theih a ni.
C. Onsite High-Voltage tuar theihna test
Calibration piah lamah 400kV 1A output hi standard AC Hipot testing atan a tha hle. Installation-a "Last Mile"-a insulation chak lohnate a hmuchhuak a, chu chuan factory test-in a man theih ngai loh transportation chhiatna emaw assembly error emaw a hmuchhuak a ni.
4. Accuracy leh Waveform A Pawimawh Chhan
Calibration atan chuan 400kV output chu a theih ang anga "thianghlim" a ni tur a ni.
Harmonic Suppression: Resonant circuit hian natural low-pass filter angin hna a thawk a, 50Hz sine wave thianghlim tak a pe chhuak thin. Hei hian VT/CVT chu real-world operating conditions hnuaiah calibrate a nih theih nan a pui a ni.
Zero-Voltage Start: Integrated controllers hian voltage chu zero atanga a sang chhoh dan tur a enfiah a, instrument transformer-a sensitive secondary windings te chu sudden inrush currents lakah a venghim a ni.
5. Testing Service Provider te tan ROI khalh
EPC contractor leh testing lab tan chuan 400kV Series Resonance Test Set portability hian inelna lama hmasawnna nasa tak a entir a ni:
Reduced Logistics: Modular components (unit khatah 60- 80 kg hnuai lam) chu standard van-ah phurh theih a ni.
Faster Setup: Reactors te rang taka inzawmkhawm chuan "ni khatah-day" test leh reporting a ti thei a ni.
Metrology Grade: Regulatory audit leh utility handover te tihhlawhtlin nan data confidence mamawh a pe.
Tawpna
Khawvel pumah 400kV grids a lo zau chhoh zel avangin, precise, on-site diagnostics mamawhna hi non-negotiable a ni. [Wuhan Huayi / Your Brand Name] ah hian kan 400kV 1A Series Resonance system te hi high-voltage challenge buaithlak ber ber te tame turin engineer a ni.
I HV testing theihna tihchangtlun turin i inpeih em? [Vawiin hian kan technical engineer te biak theih a ni] quote leh system configuration customized duh tan.