Q: Ka GIS hi 220 kV a ni. Factory-in an Type Test-a an hman voltage ang chiah khan ka test tur em ni?

A: NI LO. Field test voltage hi a hniam zawk a, chu chu "Over-stress" hmanrua, thawn chhuah leh enkawl tawhte awm loh nan a ni.

"80% Rule" tih chu:

• Factory Test: GIS hi siamtu hnenah standard withstand level 100%-ah (eg, 220 kV system atan 460 kV) test a ni.

• Field Test: Factory test voltage 80% (eg, 368 kV) kan hmang tlangpui.

• Hun chhung: A tlangpuiin 80% level-ah minute 1 vel a ni.

Engvangin nge 80%? Balance a ni. Assembly error emaw transport damage emaw hmuh theihna tur khawpa sang a ni a, mahse a hniam tawk a, a famkim lohna tenau a awm chuan insulators te chu permanent aging a thlen lo ang.