Transformer oil test a ni a .
- Di-Electric test emaw voltage test tihchhiat emaw a ni thei.
- Viscosity test 100 a ni.
- Acidity test 100 a ni.
Voltage test 10.1.
International standard 1000 a ni.
- Electrode pahnih inkarah 2.5 mm gap a awm a, voltage 25 kV hnawih chu 1 min chhung a ni.
- 2.5 mm-25 kV-1 min: Oil-ah chuan spark a awm lo, oil a OK lo, oil hi voltage level eng pawhah hman theih a ni.
- Energy PAC hian he standard hi a zawm a ni.
- Electrode pahnih inkarah 4.0 mm gap a awm a, voltage 45 kV hnawih chu 1 min chhung a ni.
Acidity test 100 a ni.
Acidity level:
- 0.5 mg KOH/gm (oil a OK.)
- 0.5 atanga 1.0 mg KOH/GM (enfiahna hnuaia awm)
- 1.0 mg KOH/mg (discard oil) a ni.
Viscosity test 100 a ni.
- Oxidation reaction a san chuan oil viscosity a sang chho zel a.
- Oxidation chu oil dissolved gas a san chuan a pung chho zel a.
- Dissolved gas analysis hmang hian oil chhunga gas dissolved chu hriat theih a ni.
- Viscosity a pun zel chuan oil chu a bulky a, a kal zawi zawi a, a insulation theihna chu a chhe zauh zauh bawk.
- Viscosity hi a hniam thei ang bera hniam tur a ni.
Insulation do theihna test .
- Japanese Standard: (Rated Voltage*2+1) KV DC chu hman a ni.