XLPE vs. PILC — engtin nge cable insulation materials te hi an awm dan a danglam?

 Jun 16, 2026

 Message pakhat dah la .

 

Q: Paper hlui-insulated lead cable (PILC) leh tunlai XLPE cable ka test mek a ni. IR result inang chiah?

 

A: Ni lo, a ni lo tak zet. XLPE leh PILC hi taksa leh chemical lamah pawh an danglam vek a, an IR range "hrisel" pawh hi order engemaw zatin a danglam a ni.

 

Thil awmzia tehkhin dan:

NihphungXLPE (Cross-linked Polyethylene) a ni a, a chhuahna hmun hi a nuam hle.PILC (Paper Insulated Lead khuh) hmanga siam a ni.
Insulation chi hrang hrangSynthetic solid polymer (plastic- ang chi) a ni.Paper tape hmanga khuh leh oil hmanga saturated
IR Range pangngai tak a niA sang hle: GΩ atanga TΩ thlengModerate: MΩ sawm atanga MΩ za tam thleng
Moisture Sensitivity a awm bawkA hniam hle (kum tam tak chhunga tui slow thing) .A sang hle (sheath breach-ah 0 Ω-ah a tla nghal vek)
Typical PI Value a niA sang hle: 3.0 atanga 5.0+ thleng.A hnuai lam: 1.5 atanga 2.0 (2.5 aia tam a awm lo)

Junior’s Rule: PILC-ah hian XLPE standard hi hmang ngai suh, chuti lo chuan paper cable tha tak tak i hnawl ang. XLPE-ah hian PILC standard hi hmang ngai suh, hei hian cable chhe nasa tak, puak tur chu a tichak thei a ni.

Inquiry thawn rawh .