Transformer bushing CTs te hi transformer an inzawm vek hmain current ratio test method hmangin test tur a ni. CTS hi transformer-a dah hmain test hmasa phawt tur a ni. A then phei chuan CTS hi test leads te chu installed bushing tawp pahnih ah connect in test a ngai thei bawk. Hei hi a harsa thei hle! CTS chu transformer-ah dah a nih tawh chuan, bushings dah luh hmain CT center-ah te testing leads lian tak (high-capacity) -testing chu lak chhuah theih a ni. A chang chuan current ratio test pawh tih theih a ni lo. CT TAP ratio te hi CT winding pum puiah voltage hmanga voltage dah a nih chuan verified theih a ni – tap voltage ratio test -- chutah chuan tap pakhat zel a voltage tlahniam zat tehna hmangin. Hei hi test awlsam tak a ni a, voltage ratio chu tap hrang hrang inkara CT turns ratio nen direct proportional a ni ang.
Mahse, he tap voltage ratio test hi current ratio test aiah chuan thlan tur a ni lo. Voltage method hi a hnuhnung ber atan ngaih tur a ni. Rated current-a hmanrua test hian service-a dah a nih chuan beisei angin a thawk thei dawn tih rintlakna a pe tam zawk. Tuna ratio method hian he philosophy hi a lantir a; Tap voltage ratio method chuan a ti lo. TAP voltage method hian installed CT-a orientation (polarity) dik tak chu a din thei lo va, primary to secondary current ratio pawh a test thei lo va, point thenkhat chu finfiah lohvin a awmtir thei bawk.
Tap voltage ratio bakah hian secondary tap current ratio test pawh tih theih a ni bawk. He test atan hian rated emaw less current emaw chu tap input hmangin inject a ni a, full CT winding a output current chu transformer action hmangin teh a ni. Autontransformer-a short-circuit impedance test tih dan hman dan nen a inang a ni.
CT polarity verify a la ngai tho. Power transformer-a CT polarity dinna atana hman dan pakhat chu "Flashing the CTS" tia sawi a ni tlangpui. He test hi transformer bushings-ah 6-to-12 volts DC hmangin tih theih a ni a, hot stick hmangin .
Test circuit chu siam la, tichhia rawh. Automobile battery hi a awlsam ber fo a, a chhan chu hnathawhna hmunah hian hnathawhna lirthei a awm tlangpui a, mahse lantern battery pawh a thawk thei bawk. Transformer winding resistance hi a tlangpuiin 12-volt car battery atanga current flow tihtlem nan a tawk a, mahse test circuit-a series (current-limiting) resistance (load box) dah belh chu test circuit eng pawhah automotive battery hmangin a tha hle.
DC test circuit hian disconnect a nih chuan voltage kick a siam dawn tih hre reng ang che. Electric shock loh nan fimkhurna tur a ni. CTS-a direct-a he test hi tih a nih chuan, flash lead connection-ah hian current-limiting resistance (load box) dah vek tur a ni. LANTERN 100 a ni.
Battery te hian internal resistance sang tak an nei a, extra series resistor an mamawh lo bawk. Power transformer-a arc flash chu transformer windings tawi tak a nih chuan a tlem thei ang-a sir lamah circuited a nih chuan a hmaa flashed a nih chuan .
CT dikna leh performance atan chuan flashing hi test duhthusam a ni lo mai thei a, a chhan chu CT core-a residual magnetism condition a awm theih avangin. Theory-ah chuan a rah chhuah theih chu a tir lama chakna a lo thlen chuan CT saturation avanga relay operation dik lo a ni thei. A theih chuan core demagnetizing hi high current hmanga DC flash test hnuah a tha hle. Residual flux chu AC test current (excitation current) chu high-current primary, emaw AC test voltage chu low-current secondary (excitation voltage)-ah zawi zawiin a paih a, secondary open circuited-a saturation-ah chauh a force a ni. Saturation point atanga AC quantity chu zawi zawiin zero-ah a tihhniam hnuah chuan residual flux chu core atangin a chhuak ang (demagnetized a ni ang).