Q: GIS test atan miten coil (reactor) rit tak tak dozens zet an phur ka hmu a. Engvangin nge CT-a kan hman angin high-voltage test transformer chauh kan hman theih loh?
A: Capacitance leh Power-ah a tla thla a ni. GIS busbar hi a bul berah chuan coaxial capacitor lian tak a ni.
Physics lam chu:
1. 220 kV GIS (capacitance sang tak nei) 50 Hz-a chakna pe tur chuan standard transformer chuan charging current Amperes za tam tak a supply a ngai dawn a ni.
2. Buaina: Transformer leh power supply chu building lian leh ton engemaw zat a rit a ngai dawn a ni. Hei hi field site-ah chuan phurh chhuah theih a ni lo.
3. The Solution (Series Resonance): Inductor (reactor) chu GIS capacitance nen series-a inzawmkhawmin Resonant Circuit kan siam a.
4. The Benefit: Resonant frequency (f=1 / (2π√LC)) ah chuan inductor leh capacitor te chu an in "cancel" chhuak thin. Power supply hian resistance avanga chakna hloh tlemte chauh a pe tur a ni.
Result: Van chhunga in fit 220V/380V generator te tak te hmangin GIS across 400 kV i siam thei.
"Conditioning Test" chu eng nge ni a, engvangin nge tih hmasak ber?
Q: Test procedure-ah chuan full test voltage-a kan kal hmain 20%, 50%, leh 80% voltage-ah kan thut a ngai tih a lang. Engvangin nge hun kan khawhral? Engvangin nge 100% ah hian kan kal nghal loh vang?
A: Conditioning Test hi "thianfai" step pawimawh ber a ni. GIS hi a installation debris atanga chhanchhuahna tura duan a ni.
"Jumping Particle" tih Trap hi a awm a:
1. Installation puan in chu eng ang pawhin fai mah se, a chhungah hian thir leivut emaw, sam emaw te tak te a awm thei.
2. 100% Voltage-a i kal nghal chuan, chu particle chu high-stress area-ah direct-in a zuang lut ang a, insulator kaltlangin permanent, destructive arc (puncture) a siam ang.
3. The Conditioning Logic: Voltage hniam zawk (eg, 50% minute 5 chhung) a vawn tlat avangin electric field hian heng particle te hi zawi zawiin a "dance" tir thin. Hei hian Particle Traps (tank hnuai lama field hniam-field area)-ah a hruai lut a, chutah chuan conductor-te atanga him takin an inhlat a ni.
Thupui: Conditioning hian insulation a test lo; electric hmangin insulation a tifai thin.