Eng instrument chi nge SFRA testing tih a, engineer chuan eng feature nge a zawn tur?
SFRA test set chu specialized two-port network analyzer a ni. RBX-H tester hian transformer chhunga windings-te characteristic parameters a teh a, khawvel-ram hmahruaitute tana siam sound internal fault frequency response analysis (FRA) method hmangin, internal transformer fault dik taka teh theih a ni. SFRA tester hian laptop leh chip microprocessor precision measurement system a nei a, a compact a, hman a awlsam a, test analysis function kimchang tak a nei bawk.
|
Parameter a ni |
Range a rawt a ni |
Engvangin Nge A Pawimawh |
|
Frequency range a ni |
10 Hz – 2 MHz (min) inkar a ni. |
Core, winding, leh lead region te a huam vek |
|
Dynamic range a ni |
>100 dB a ni |
Band zawng zawngah sensitivity a tichiang |
|
A chhuahna tur impedance a awm |
50 Ω (coaxial) a ni. |
Connection repeatable neih theihna tur standard |
|
Sweep points a ni |
1000 aia tam emaw a tlukpui emaw (log spacing) . |
Peak detection atan resolution tling tak a ni |
|
Measurement dik tak a ni |
± 0.5 dB mag, ± 1℃phase a ni |
Inter-phase tehkhin dan rintlak |
|
Port configuration siam dan tur |
2-port (transmission + reflection) a awm bawk. |
Characterization kimchang tak a nei thei |
Accessories hmantlak tak tak checklist:
• Coaxial test leads (10 m, 15 m, 20 m set) a ni a, a man pawh a tlawm hle.
• Bushing terminal atana hman tur Alligator-to-BNC adapter te
• Leilung leia inzawmna kit
• Temperature/humidity logging (record traceability atan) .
• Correlation coefficient thlirletna leh report siamna atana software
Pro tip tur chuan:Instrument-a input impedance chu coaxial cable-te impedance nen a inmil em tih enfiah fo ang che. 50 Ω mismatch hian 500 kHz aia sang standing-wave artifact a rawn luh tir a, chu chuan "deformation" indication dik lo a thlen a ni.