Duval Triangle hi eng nge ni a, transformer fault te hi engtin nge a classified?

 May 15, 2026

 Message pakhat dah la .

 

Q: DGA hrilhfiahnaah hian "Duval Triangle" chungchang hi ka hre nasa hle. Engtin nge a thawh?

A: Duval Triangle (Michel Duval, IREQ siam, tuna IEEE C57.104) hi ternary diagram hmanga DGA fault classification atana graphical method hman lar ber a ni.

Gas ratio pathum (Triangle 1 - mineral oil) te hi:

• %CH4=CH4 / (CH4 + C2H2 + C2H2) × 100 a ni

• %C2H4=C2H4 / (CH4 + C2H4 + C2H2) × 100 a ni

• %C2H2=C2H2 / (CH4 + C2H2 + C2H2) × 100 a ni

Zone a ni

Fault chi hrang hrang

Hrilhfiahna

PD a ni

Partial Discharge a ni

Low-energy corona, void-a meialh chhuak

D1

Energy hniam-A chhuahna

Sparking, tracking (glow discharge) te a awm a.

D2

Energy tamna-Scharge

Arcing with power chu a zui-through

T1

A lumna < 300℃a ni

Insulation lum lutuk (winding emaw core emaw) .

T2

A lumna chu 300℃–700℃a ni

Hot spot, electric connection tha lo

T3

A lumna > 700℃a ni

Hot spot na tak, arcing + thermal a awm thei

DT

Mixed Thermal + Discharge a awm bawk

Combination tihsual a ni

Entirnan diagnosis: 1.1.

150 MVA transformer: CH4=180 ppm, C2H4=280 ppm, C2H2=5 ppm

%CH2=38.7%, %C2H4=60.2%, %C2H2=1.1%

→ T2 zone-ah a tla → thermal fault 300–700℃.

C2H4 sang + C2H2 hniam → bolted connection tha lo emaw tap-changer contact emaw a nih a rinawm.

Action: Tap-changer contacts te enfiah rawh. C2H4 a san zel chuan outage schedule rawh.

Duval Triangle dangte chu:

Triangle a awm

Dilna

Key Inthlauhna

Triangle 1 a ni

Mineral oil transformer (standard) hmanga siam chhuah a ni.

CH4, C2H4, C2H2 te pawh a awm bawk

Triangle 2 a ni

Thermal fault zone tihthianghlim a ni

CH4, C2H4, C2H3 te pawh a awm bawk

Triangle 3 a ni

Temperature hniam-a thermal fault a awm

C2H4, C2H3, CH4

Triangle 4 a ni

Load Tap Changer (LTC) te chu a rawn chhuak leh ta a ni.

Gas inang, zone boundary hrang hrang

Triangle 5 a ni

Natural ester (thlai hriak) 1.1.

Ester oils te tan ramri siamrem a ni

A tihkhawtlai theihna:

• Detection limit aia sang hydrocarbon gas pathum tal a mamawh.

• Gas pakhat > ​​HC zawng zawng atanga 80% a nih chuan rintlak lo zawk.

• Fault chi hrang hrang a ruala awm tam tak a thliar hrang thei lo.

• Gas siam chhuah zat (ppm/day emaw ppm/month) nen hmang fo ang che.

Inquiry thawn rawh .