VLF Hipot test method leh AC resonant test te hi a pawimawh a, power equipment enkawl dan, himna leh hnathawh dan tur test dan tlangpui a ni. An inkar danglamna chu a hnuaia point hmang hian kan zir thei a ni.
1. Test principle leh test frequency.
VLF hipot test frequency: 0.1Hz (or 0.02- 1Hz), analog power frequency, mahse a rei hle.
VLF Hipot Test Principle: Dielectric loss leh partial discharge detect ultra-frequency voltage hniam tak, medium leh low voltage cable (35 kV aia tlem emaw a aia tlem emaw tan pawha hman tlak) hmangin detect rawh.
AC resonant test frequency: 30-300 Hz (Power frequency 50/60 Hz bulah a awm).
AC Resonant Test Principle: Reactor hi cable capacitive reactance compensate nan hman a ni a, high voltage resonance a siam a, capacity cable lian tak tak ( 110 kV aia tam emaw a tlukpui emaw) high voltage test a nei thei bawk.
2. Application scenario tehkhin dan .
|
|
VLF 100 a ni.Hipot test a ni a. |
AC resonant test a ni a. |
|
TYPE chu cable a ni. |
35 kV aia tlem emaw a aia tlem emaw) |
110 kV aia tam emaw, a tlukpui emaw |
|
TEST Tum 1.1. |
Insulation defect hriat theihna, aging evaluation . |
Handover test, compressive strength verification . |
|
Portable . |
kg 80 aia tlem emaw a aia tlem emaw . |
500 kg aia tam emaw a tlukpui emaw |
|
nihphung pangngai |
IEEE 400.2,IEC 60502 ah a awm. |
IEC 60840,GB/T 3048.8 a ni. |
3. thlan dan tur rawtna .
VLF duh ber:
Cable inspection, rush repair, emaw space-35 kV hnuai lam scenario tlemte.
Resonance duh zawk:
Voltage sang tak cable factory test, GIS terminal connection test.