Q: On-line DGA monitor ka install tur em ni, a nih loh leh lab-ah oil sample thawn chhunzawm tur em ni?
A: Method tin hian chanvo hrang hrang an nei a. Duhthlan tur chu transformer criticality, fault history, leh budget-ah a innghat a ni.
|
Khaikhinna |
Laboratory-ah DGA a awm a |
On-line DGA Monitor ah a awm |
|
Interval a ni |
Quarter tin atanga kum tin thleng |
Continuous (min 30 danah – darkar 24 chhung) . |
|
Gas hmuhchhuah a ni |
Gas 7+ zawng zawng (H2, CH4, C2H3, C2H4, C2H2, CO, CO2, O2, N2) te hi a ni. |
A tlangpuiin gas 5–9 (model hrang hrangah a danglam) . |
|
Dik chiahna |
A sang (lab GC: ±1 ppm) a ni. |
A hniam lam (Lehkha chhiar zat ±5–15%) . |
|
Trend sensitivity a ni |
Sampling frequency atanga tihtlem a ni |
- hian load-induced changes a capture tha hle |
|
Capital senso a ni |
~Sample khatah $50–100 a ni |
Monitor pakhatah $5,000–$30,000 vel a ni |
|
Operating cost a ni |
Kum khatah $200–1,000 (quarter tin) a ni. |
Kum khatah $500–2,000 (consumables, calibration) a ni. |
|
A tha ber atan |
Fleet tenau ( Unit 10 aia tlem emaw, a tlukpui emaw); non-critical a ni lo |
>100 MVA, EHV/UHV a ni a; hla; hriat-sualna |
Thiltih dan tha ber - hybrid approach:
1. Transformer pawimawh ber 10–20% zingah on-line monitor dah tur a ni.
2. Unit dang zawng zawngah quarterly lab DGA hman tur.
3. Thla 6–12 danah on-line monitor te chu lab sample hmangin cross-validate thin ang che.
4. Developing fault hmuhchhuah a nih chuan lab sample lak nghal la, confirmation + full spectrum atan.