Dielectric absorption test dan tur .
Dielectric-absorption test-ah chuan constant potential source atanga voltage pek chhuah chu insulation pumpuiah a awm a. Test voltage hman chu measurable current readings hmuh theih nan insulation resistance test aiin a sang zawk a nih chuan sign a ngai thei bawk. Potential source chu a chunga kan sawi tawh ang khan MEG-ohmmeter emaw, high-voltage power supply test mek specimen-in current a siam dan tarlanna ammeter nei emaw a ni thei. Voltage hi hun rei tak chhung, minute 5 atanga 15 thleng hman a ni a, insulation resistance emaw leakage current emaw chu a hun takah lak a ni.
Test data chu insulation a tha a nih chuan test a kal zel chuan a insulation resistance langsar tak chu a sang chho zel dawn tih a ni. Insulation-resistance test ang lo takin, dielectric absorption test result chu test mek insulation volume leh temperature atanga innghat lo a ni. Dielectric absorption test atan chuan minute khat interval tina record value te chu log-log paper ah resistance versus time atan coordinate neiin plot a ni. Curve lo chhuak slope hian insulation condition a hriat theihna tur a pe tha hle. Insulation system tha tak chuan slope a nei ang a, chu chu straight line a ni ang a, hun nena inzawm chuan a pung zel ang. Insulation system tha lo tak characteristic slope chu hun nena inzawma flatten out curve a ni ang.
Polarization index test dan .
Polarization index hi dielectric absorption test hmanga specialized hman a ni a, a hman dan tur pawh a inang lo hle. Index chu voltage hman hnua hun hrang hranga insulation resistance ratio a ni a, a tlangpuiin minute 10-ah insulation resistance chu minute 1-ah a ni. Polarization-index testing hman hi a tlangpuiin rotating machine, cable leh transformer-ah chauh a awm thin. Polarization index 1.0 aia tlem chuan a tarlang a ni.
hmanrua chu service-a dah hmain enkawl a ngai tih. Thil hmanrua chi hrang hrang atan polarization index hrang hrang atan reference a awm a, Table 1-2-ah pawh a awm bawk. Electrical power leh distribution equipment leh system hrang hrangte tana pawm dan Specifications Neta 1999 leh rotating machinery-a insulation resistance (IEEE STD. 43-2000) test-na atana practice rawt te chu hmanrua chi hrang hrang polarization index-a hman theih tur reference a ni. Polarization index test hi minute 10 chhung a ni. Insulation resistance chu minute 1 hnuah record a ni a, chutah chuan minute 10 hnuah record a ni leh bawk. Polarization index chu a hnuaia equation-a kan hmuh ang hian minute 10 leh minute 10 chhunga chhiar tur quotient a ni:
pi=Rio/r, (Dimensionless) ah hian:
Pi=Polarization Index .
r=dodalna.
Transformer-a polarization index-te tan chuan pawm theih value chu 2 emaw a aia sang emaw a ni ang a, 2 leh 1 inkar value chuan marginal condition a tarlang ang a, 1 hnuai lam value chuan condition tha lo a lantir ang. Insulation resistance reading an tih zawh hnuah test voltage chu zero-ah an kir leh a, insulation chu an discharge leh a ni.