Q: HV testing atan hian SR circuit hian engtin nge hna a thawh a, engvangin nge voltage a amplify?
A: Resonance-ah chuan: ωL=1/(ωC) a ni. Impedance la awm chhun chu circuit resistance R. V_out=V_in × Q. He voltage amplification hi SR HV testing bulpui ber a ni.
Circuit: VFD → Exciter TX → Reactor L → Load C (specimen) a ni a, a chhuahna tur hmun leh a hmanna tur hmun chu a inthlau hle.
Maths chu:
• Resonance-ah: X_L=X_C → reactance zawng zawng=0. Q=X_L / R=(1/R)√(L/C)
• V_out=V_in × Q. P_in=P_out / Q. A chhuah dawn chuan a chhuak leh ta a.
Khawvel entirnan - tak tak - 10 km 110 kV XLPE cable:
• C=2 μF, target V=128 kV a ni. A rilru a buai em em a, a rilru a hah em em bawk a. F_res=15.9 Hz.
• Q=50 → exciter hian 128/50=2.56 kV chauh a mamawh.
• A chhuahna tlukpui: 2,048 kVA. Input tak tak: ~6.5 kW (generator te tak te atanga lak).
Resonance neih theihna tur condition pathum:
1 Tuning: ω2=1/(L·C) a ni. 2 A nghetna: ±0.5 Hz. 3 Thianghlimna: THD < 5% (tank filter harmonics).
A thatna pawimawh ber: Ferranti effect a ti bo (series inductor hian load capacitance a compensate).