AC Hipot test hian eng tak nge a finfiah a, engvangin nge "tichhe thei" mahse a pawimawh loh?
AC Hipot test hian second 60 chhungin AC voltage rated voltage aiin nasa takin a sang zawk a ni. Insulation hian service-a a tawn theih tur overvoltage na ber pawh a tuar thei tih a finfiah a ni.
Test dang nena khaikhin chuan:
|
Fiahna |
Eng Nge A Hrilh Che |
A tihkhawtlai theihna |
|
IR / PI a ni |
DC low voltage-a insulation dinhmun |
AC stress distribution a simulate lo |
|
Tanδ / PF tih a ni |
Dielectric hloh a ni |
Moisture-ah a sensitive a, gross defects-ah a sensitive lo |
|
PD tehna a ni |
Partial discharge hnathawh a ni |
Total withstand atan chuan pass/fail a awm lo |
|
AC Hipot a ni |
Overvoltage chhe ber-case-ah a dam thei ang em? |
Defect localize theih loh (pass/fail chauh) |
"Tichhe thei" nature chuan heti hian a sawifiah a:
• Insulation hrisel → chhiatna awm lovin a kal (non-destructive to good insulation).
• Insulation chak lo → test laiin a chhe (intentional - thlipui tleh lai aiin factory-ah a tha zawk).
IEC pawm dan (IEC 60060-1):
• Second 60 chhunga test neih chhung hian disruptive discharge (flashover emaw breakdown) a awm lo.