Cable fult locator (Time Domain Reflectometry) te hi eng nge ni?

 Jun 26, 2026

 Message pakhat dah la .

 

Q: Mite chuan TDR hi "Cable Radar" tiin an ko thin. Engtin nge laih lohvin dik lohna a hmuh theih?

 

A: TDR hian low-voltage pulse (<100V) and listens for the reflection. Any impedance change causes a bounce-back wave.

TDR screen chhiar dan tur:

Waveform Shape a ni

Awmzia

Fault chi hrang hrang

Chunglam (Positive) a ni.

Impedance → A tawp thei lo

Circuit hawn / Cable cut theih a ni

A hnuai lam (Negative) .

Impedance → Zero a ni

Short Circuit / Phase-Leiah a awm a

Flat Wave a ni

Impedance chu Constant a ni

Cable hrisel tak a ni

Logic: Distance=(Velocity × Time) / 2. TDR hian "dead shorts" leh "broken wires" te chu awlsam takin a hmu thei.

 

"Thumping" (High Voltage Surge) tih hi eng nge ni?

 

Q: TDR hian cable hrisel tak a lantir a, mahse breaker chu a trip zel thung. Engvangin nge "Thump" a nih?

A: TDR hian high-resistance insulation crack chu "a hmu" thei lo. Fault hmunah hian artificial arc kan siam a ngai a ni.

Thumping tih dan tur chu:

1. Charge: Equipment hian high-voltage capacitor lian tak (The Thumper) a charge thin.

2. Discharge: Cable chhungah pulse lian tak pakhat (eg, 15 kV) ah energy a chhuah tir.

3. The Arc: Pulse hian defect chu a hit a, Artificial Arc (Flashover) a siam a.

4. Signal: Arc hian temporary short angin hna a thawk a, TDR wave a lantir a ni.