Q: Primary-ah P1/P2 ka hmu a, secondary-ah S1/S2 ka hmu bawk. A awmzia tak chu eng nge ni?
A: Polarity hian current kalna tur relative direction min hrilh a. AC hian direction a thlak avangin eng kawng nge "forward" tih hriat nan reference kan mamawh a ni.
Subtractive Polarity a awm chuan:
Rule: Current IN to P1=S1 atanga current OUT chu instant khatah.
P1/P2: Terminal hmasa berte. S1/S2: Secondary terminal hrang hrang.
Analogy: Darthlalang pakhat han mitthla teh. P1 chhungah i kal chuan i reflection chu S1 atangin a chhuak chhuak thin.
Engvangin nge Polarity hi a pawimawh em em? Reverse a nih chuan eng nge thleng ang?
Q: Magnitude hi a inang vek a nih chuan engvangin nge direction hi a pawimawh?
A: Directional leh differential protection atan chuan reversed polarity hi chhiatna a ni.
"Betrayal" Effect (Differential Protection) a awm dan chuan:
Dik: 100A In - 100A Out=0A danglamna (Relay hlim). ✅ a ni
Reversed: Relay hian 100A In a hmu a, -100A Out → 200A internal fault angin a lang. ❌ tih a ni
A rah chhuah: Instant false trip. Downtime vangin economic loss nasa tak a awm.