Q: No-load loss hi eng nge ni tak tak a, test kalphung chu eng ang nge a nih?
A: No-load loss (P₀), iron loss emaw core loss emaw tia sawi bawk hi transformer chu secondary open-circuited-a rated voltage leh frequency-a energy pek a nih chuan power hman zat a ni.
No-load loss-a component hrang hrangte:
• Hysteresis hloh (P₀ ~60–70%) - chakna chu magnetic domains (∝ f × B1·6) tidanglam turin.
• Eddy current hloh (P₀ atanga ~25–35%) - lamination-a current circulating (∝ f2 × B2 × t2).
• Primary winding-ah dielectric hloh (~1–5%) + I2R (a tlem hle).
Test dan tur (IEC 60076-1 / IEEE C57.12.90):
|
Rahbi |
Thiltih |
Notes te chu |
|
1 |
Open-circuit secondary (LV lam) ah a awm a. |
Safety - secondary hian voltage hlauhawm tak a thleng thei tih enfiah rawh |
|
2 |
Rated Uₙ rated f ah primary (HV lam) ah hnawih rawh . |
Waveform THD < 5% a ni. |
|
3 |
A tehna V, I, P2 |
Class 0.2 power analyzer hmang rawh |
|
4 |
I2 chu rated current % angin record rawh |
A tlangpuiin 0.5–5% . |
|
5 |
20℃reference ah dik takin a awm |
P2 tan chuan siamthatna tenau tak a ni |
P2 value tlangpui: 1.1.
• A insem darh dan (100 kVA–2.5 MVA): P1 atanga 0.3–0.8%
• A chakna (medium power) (5–50 MVA): 0.15–0.4% a ni.
• Power lian tak (100–500 MVA): 0.08–0.2% a ni.
• Amorphous core: grain-oriented steel aiin ~70% in a hniam zawk
P1 sang hian: core degradation, interlaminar shorts, joint tha lo, leh over-excitation a kawk a ni.
Pawmna: tehna P Guaranteed + 15% aia tlem emaw, a tlukpui emaw (IEC 60076-1).