Q: Load loss chu eng nge ni a, eng thilin nge a thlen a, engtin nge kan teh ang?
A: Load loss (Pₖ) chu load current leh stray flux avanga windings-a power dissipated, I2 nena inmil a ni.
Load loss-a component hrang hrangte:
• I2R hloh (Pₖ atanga ~70–85%) - DC do theihna Joule heating.
• Winding-a eddy current hloh (~10–20%) - vun + proximity effect.
• Structural parts (~5–10%) - tank, clamp, core bolt-a stray hloh.
Test kalphung - Short-Circuit Impedance Test:
|
Rahbi |
Thiltih |
Notes |
|
1 |
Short-circuit secondary (LV lam) a ni. |
Heavy-duty shorting bar hmang rawh |
|
2 |
Primary ah voltage tihhniam hmangin hnawih rawh |
Zero atanga tan tur; rated current-ah tihpun a ni |
|
3 |
A tehna Vₖ, Iₖ=I_rated, Pₖ |
Vₖ hi a tlangpuiin Uₙ atanga 5–15% a ni |
|
4 |
Record Vₖ%=Vₖ / Uₙ × 100% a ni. |
Impedance voltage percentage atanga chhut a ni |
|
5 |
Pₖ chu 75℃thleng dik rawh |
Pₖ(75) = Pₖ(T) × (235+75)/(235+T) |
Pₖ pangngai lo chuan:
• > +15% guaranteed → high-resistance connection, strand chhe, tap dik lo.
• Trending upward → loose connection siam chhuah, winding deformation (eddies) te.
• Vₖ% a inthlak > ±10% → winding deformation (IEC limit) a ni.
Acceptance: Pₖ 75 degree-a guaranteed + 15% aia tlem emaw, a tlukpui emaw ; Vₖ% chu ±10% chhungah guaranteed a ni.