DGA-ah hian eng gas nge enfiah a nih a, gas tin hian eng nge a lantir?

 May 15, 2026

 Message pakhat dah la .

 

DGA-a key gas pasarih te hi engte nge ni a, eng failure mode nge an inmil?

 

DGA hian transformer oil-a gas pawimawh pasarih a hmin chu a enfiah ṭhin. Gas tin hi energy level leh fault type bik nen a inzawm a ni.

Gas a ni

Formula a ni

Energy Threshold a ni

Fault chi hrang hrang inzawmkhawm

Hydrogen a ni

H₂

Low / Medium a ni

A then a chhuak (corona), electrolysis, rust

Methane hmanga siam a ni

CH4

Hniam

Sparking / chakna hniam-arcing

Ethane chuan a rawn ti a

C₂H₆

Hniam

Thermal oil tihchhiatna ( .< 300°C)

Ethylene a ni

C₂H₄

Sang

Thermal hot spot (300℃–700℃) - winding a lum lutuk

Acetylene a ni

C₂H₂

A sang hle mai

Arcing (>700℃) - fault gas hlauhawm ber a ni

CO

CO

Hmanrua

Cellulose (paper) thermal degradation (>200℃a ni ) .

CO2 a ni

CO2 a ni

Hniam

Cellulose kum pangngai (CO2/CO ratio hmang) .

Diagnostic inzawmna pawimawh tak takte:

• H2 chauh emaw H2 + CH4 → Partial discharge (corona).

• C2H2 → Arcing tih a ni. Trace amounts ( 1–5 ppm aia tam emaw, a tlukpui emaw) pawh hian hmalakna nghal a ngai a ni.

• C2H4 dominant → Temperature sang-temperature thermal fault (windings lum lutuk) a awm.

• CO2/CO > 10 → Kum upa lam pangngai; CO2/CO < 3 → Paper-a thermal fault active tak a awm.

Background gas level hrang hrang: 1.1.

• Transformer zawng zawng hian hnathawh dan pangngai atanga background gas engemaw zat an nei vek.

• Trending hi absolute value pakhat chauh aiin a pawimawh zawk.

• Thla tin 20% a san chuan absolute value te chu alarm threshold hnuai lam ni mahse ngaihven a ngai a ni.

Gas siam chhuah leh fault energy:

Energy hniam → H2 → CH4 → C2H3 → C2H2 → C2H2 ← Energy sang

(PD) (thermal) (arcing) tih a ni.

Inquiry thawn rawh .
Inquiry thawn rawh .