DGA-a key gas pasarih te hi engte nge ni a, eng failure mode nge an inmil?
DGA hian transformer oil-a gas pawimawh pasarih a hmin chu a enfiah ṭhin. Gas tin hi energy level leh fault type bik nen a inzawm a ni.
|
Gas a ni |
Formula a ni |
Energy Threshold a ni |
Fault chi hrang hrang inzawmkhawm |
|
Hydrogen a ni |
H₂ |
Low / Medium a ni |
A then a chhuak (corona), electrolysis, rust |
|
Methane hmanga siam a ni |
CH4 |
Hniam |
Sparking / chakna hniam-arcing |
|
Ethane chuan a rawn ti a |
C₂H₆ |
Hniam |
Thermal oil tihchhiatna ( .< 300°C) |
|
Ethylene a ni |
C₂H₄ |
Sang |
Thermal hot spot (300℃–700℃) - winding a lum lutuk |
|
Acetylene a ni |
C₂H₂ |
A sang hle mai |
Arcing (>700℃) - fault gas hlauhawm ber a ni |
|
CO |
CO |
Hmanrua |
Cellulose (paper) thermal degradation (>200℃a ni ) . |
|
CO2 a ni |
CO2 a ni |
Hniam |
Cellulose kum pangngai (CO2/CO ratio hmang) . |
Diagnostic inzawmna pawimawh tak takte:
• H2 chauh emaw H2 + CH4 → Partial discharge (corona).
• C2H2 → Arcing tih a ni. Trace amounts ( 1–5 ppm aia tam emaw, a tlukpui emaw) pawh hian hmalakna nghal a ngai a ni.
• C2H4 dominant → Temperature sang-temperature thermal fault (windings lum lutuk) a awm.
• CO2/CO > 10 → Kum upa lam pangngai; CO2/CO < 3 → Paper-a thermal fault active tak a awm.
Background gas level hrang hrang: 1.1.
• Transformer zawng zawng hian hnathawh dan pangngai atanga background gas engemaw zat an nei vek.
• Trending hi absolute value pakhat chauh aiin a pawimawh zawk.
• Thla tin 20% a san chuan absolute value te chu alarm threshold hnuai lam ni mahse ngaihven a ngai a ni.
Gas siam chhuah leh fault energy:
Energy hniam → H2 → CH4 → C2H3 → C2H2 → C2H2 ← Energy sang
(PD) (thermal) (arcing) tih a ni.