Engtin nge tanδ test hi bushing-ah hman a nih a, eng physical quantity nge kan teh?
Capacitive bushing (OIP emaw RIP emaw) tan chuan tanδ test hian conductor leh tap layer inkar insulation-a dielectric loss te a teh a, tap layer leh ground flange inkarah te a teh bawk.
Taksa lam thu bul: 1.1.
Bushing hrisel tak chu capacitor tha tak ang maiin a che thin. Tanδ=Iᵣ / I꜀ (resistive current/capacitive current) tih hi a ni.
|
A tehna |
Terminal hrang hrangah a awm |
Eng nge A Assess |
|
C1 & PF/DF (UST) te a ni. |
Center conductor ⇔ Tap rawh |
Conductor leh tap layer inkarah hian main insulation - paper/oil dielectric a awm |
|
C2 & PF/DF (GST) te a ni. |
Ground flange chu ⇔ tap rawh |
Oil gap & pawn lam insulation - tap atanga grounded flange thleng |
Typical values (thar, 20 degree-ah ): .
• C1 tan PF: < 0.5% (oil-impregnated paper) a ni.
• C2 tan PF: < 1.0% (oil gap) a ni.
• Capacitance tolerance: nameplate value atanga ±2–5% chhunga awm tur a ni