Q: DGA atan hian transformer oil hi engtin nge sample tur a ni a, sample laksual tam ber chu engte nge ni?
A: DGA result hi sampling procedure ang chauha rintlak a ni. Sample contaminated emaw aerated emaw hian result dik lo a siam thei a ni.
Sampling lakna hmun:
• Bottom valve atanga sample lak fo thin (sediment leh gas rit zawkte chu chutah chuan an khawlkhawm thin).
• Top oil fill port atang hian sample ngai suh.
|
Thil |
A sawifiahna |
Chhan |
|
Syringe hmanga siam a ni |
Glass syringe 20–50 mL, Luer lock hmanga siam a ni |
Air-tight sample, boruak entrainment awm lo |
|
Sampling bottle a ni |
500 mL amber glass, Teflon-lined cap a ni |
Headspace-a thlawna dahkhawm leh phurh chhuah |
|
Tubing a ni |
PTFE (Teflon) - PVC emaw rubber emaw LO |
PVC hian hydrocarbon a hip lut a; rubber chuan a chhuah tir thin |
|
Cooling box a ni |
Insulated, < 10℃a ni |
Microbial gas siam chhuah a tikhawtlai |
Step-by-step sample lakna:
1. Bottom valve hawng la, oil 1–2 L chu bawlhhlawhah luang chhuak rawh.
2. PTFE tubing chu sampling valve-ah connect rawh.
3. Tubing chu oil hmangin second 10–15 chhung silfai ang che.
4. Syringe needle chu flow stream-ah dah la; 20 mL zawi zawiin lakchhuah - bubbles pumpelh rawh.
5. Micro-bubbles te chu displace turin syringe kha tap la; 1–2 mL chhuah tir; Luer cap hmanga seal a ni.
6. Light-proof bag-ah khuh (UV hian oil-ah H2 a siam chhuak).
Thil tihsual pawimawh tak tak:
|
Tihsual |
A rah chhuah |
|
Top air vent atanga sample lak a ni |
Gas concentration hi a aiawhtu a ni LO |
|
Waste oil luang chhuak hma lutuk tihtawp |
Valve neck atang hian stagnant oxidized oil a la chhuak thin |
|
Rubber emaw PVC tubing emaw hmangin |
C2H3 dik lo, CH4 peaks (leaching) te chu a dik lo. |
|
Syringe chhungah air bubble dah chhuah |
H2 leh O2 rintlak loh (air contamination) . |
|
Sample chu ni êng direct-a dah |
UV hian H2 → false PD indication a siam chhuak thin |
|
Refrigeration tel lovin darkar > 48 chhung tihkhawtlai |
Biological activity hian H2, CH4, CO2 a siam chhuak thin |
Transport: Darkar 48 chhungin lab-ah 4–10 degree-ah thawn tur a ni.