Q: Test site thlengin engkim ka phur vek tur a ni. Eng system nge a tenau zawkah a inthen?
A: SR hian hands-down a hneh. Modular a ni - reactor tin hi piece hran a ni. Test transformer chu tank lian tak pakhat a ni.
A rih zawng tehkhin dan - 100 kV class:
|
Thil |
Transformer hmanga test a ni |
Series Resonant System hmanga siam a ni |
|
Main unit a ni |
100 kV TX tank: kg 800–1,500 vel a ni |
VFD + exciter: kg 150–250 vel a ni |
|
Reactor te pawh a awm |
N/A |
3 × HV reactor: kg 100–200 ve ve a ni |
|
Control box ah hian a awm |
50 kg (built-in a chang chuan) . |
VFD unit ah pawh a tel |
|
Voltage divider a ni |
20 kg a ni |
20 kg a ni |
|
Cable hmanga siam a ni |
30 kg a ni |
30 kg a ni |
|
Belhkhawm |
900–1,600 vel a ni |
500–900 kg vel a ni |
|
Pieces phur tur |
1–2 lian tak tak a ni |
5–7 enkawl theih a ni |
Test site-a piece tin hian eng nge a awmzia:
|
Them |
Buk |
Tuin nge A phurh |
|
VFD unit (wheel) te chu a awm a. |
150–250 kg vel a ni |
Rolls on wheels / cart te tak te |
|
Reactor (a pakhat zel) 1.1. |
kg 100–200 vel a ni |
Mi 2 emaw wheel dolly emaw a awm thei |
|
Exciter TX a ni |
50–80 kg vel a ni |
Mi 1–2 te an ni |
|
Voltage divider a ni |
20 kg a ni |
Mi 1 an awm |
|
Cable hrang hrang a awm |
30 kg a ni |
Cable roll khatah mi 1 an awm |
Khawvel tak tak-: 3rd floor-ah TX test rawh? Darkar 2 chhung zet chu sawn tum rawh. SR system a ni em? Mi pahnih chuan minute 10 chhungin reactor pakhat chu chung lamah an phur a.