Q: Frequency-tuned leh inductance-tuned resonance system te hi eng nge an danglamna?

 

A: VFSR hian inverter frequency (20–300 Hz) a siamrem thin. VSR hian reactor core gap chu 50/60 Hz ah a siamrem thin. Tin, thatna hrang hrang an nei vek a.

Parameter a ni

VFSR (Variable Frequency) tih a ni.

VSR (Variable Inductance) tih a ni.

Tuning element a ni

Inverter frequency (electronic) hmanga siam chhuah a ni.

A rilru a buai em em a, a rilru a hah em em bawk a. Movable reactor core (mechanical) .

Tuning range a awm

A zau hle: 20–300 Hz

A tawi zawk: inductance ratio 2:1 atanga 5:1 inkar a ni

Tuning speed a ni

< 1 s (electronic sweep)

10–60 s (motor-driven core) a ni.

Frequency atanga chhuak

Variable (50/60 Hz ni lo) 1.1.

50/60 Hz ah tihfel a ni

Waveform thianghlimna

A tha, output filter a mamawh

Power frequency thianghlim - tha tak a ni

Reactor khatah a rit zawng

Lighter (fixed core) a ni.

A rit zawk (movable mechanism) 1.1.

Hman senso (system) 1.1.

A sang zawk (VFD inverter) a ni.

Power rating hniam takah chuan a hniam zawk

PD tehna a ni

Filter nen a tha

A tha hle (inverter ri a awm lo)

Cable test rei tak neih a ni

A tha hle (f hniam hian current a tihtlem)

A tha (L range hmanga tihkhawtlai) .

Standard zawm a ni

IEC 60060-3 chuan 20–300 Hz a phalsak a ni

Direct 50/60 Hz a ni

 

Hybrid system: reactor tap hmanga coarse tuning + narrow-band VFD (45–65 Hz) hmanga fine tuning.

Rule of thumb chu: 1.1.

• A bik takin cable < 5 km → VFSR (30–300 Hz) a ni.

• GIS / cable tawi 50 Hz → VSR (fixed frequency) a awm thei.

• Flexibility sang ber (cables + GIS + TX) → VFSR 20 Hz thlenga tlahniam.