 Message pakhat dah la .

 

Installation-a dah current transformer physical condition leh electrical characteristics nemnghet turin. CT chu kawng engkimah (primary leh secondary) system nen a inzawm tha em tih enfiah rawh.
 
Test hmanrua mamawh:
Insulation tester 1000 a ni.
Polarity tester 1000 a ni.
Digital hniam ohmmeter 1000 a ni.
Tuna a chhuahna hmun, multimeter .
Variac, step-Up transformer (0-2KV)
Primary current injection set a ni a.
Insulation do theihna test:
Voltage chu 1000 inkarah a apply tur a ni.
- primary atanga secondary plus ground (Switchgear test neih laiin khuh a ni).
- primary plus ground atanga secondary a ni.
- Secondary core atanga core.
.
Polarity test tih hi a ni.
Polarity test chu CT primary leh secondary-a polarity marking confirm a, drawing nen a inmil tih finfiah a ni. more ever it is giving an idea, engtin nge secondary te chu a connect theih ang a, chu chuan protection a siam ang (directional, differential ang chi)
leh metering function dik tak a awm bawk.
Isolate CT Secondary chu load atang hian isolate la, circuit connection siam la, close a kan hmuh ang hian primary a battery switch connected chu hawng rawh. Observe Pointer chu polarity dik tak hmuh theihna tura hawn laiin closing leh –ve direction a kal laiin +ve direction a kal a ni.
 
Burden Test: (A duh duh test) .
Burden Test chu CT-a connected burden chu rated burden chhungah a awm tih chian a ni a, nameplate-a hriat chhuah a ni. CT a rated secondary current chu inject a, CT terminal atanga load side lam hawiin CT secondary chu connected load zawng zawng nen isolate la, injection point zawng zawngah voltage drop chu en rawh. A phurrit VA chu, burden VA=voltage drop x rated CT sec. Tun. A huam chin:
Calculated burden chu rate CT burden aiin a tlem zawk tur a ni.
Note: Ammeter selector switch chu test chhung hian phase hrang hrangah a awm tur a ni. High-Impedance relay te chu test chhung hian short tur a ni.
 
Magnetization curve test: (a duh duh test) .
mag a ni. Curve Test chu CT-a magnetization characteristics chu nameplate specification hmanga nemngheh a ni.
He test hi ratio test hma leh secondary resistance leh polarity test hnua tih tur a ni a, a chhan chu residual magnetism chu DC test (polarity, resistance) avanga core-ah dah a nih avangin, chu chuan ratio test-ah error additional a thlen a ni. He test atana hman meter te hian RMS tehna dik tak an nei tur a ni.
Circuit connection chu primary tarlan angin test neih chhung hian hawn tur a ni.
Demagnetisation: 1.1.
Test i tan hmain secondary terminal-a voltage inject-in core chu demagnetize-in, voltage increment tlemte hmanga current-a increment nasa tak awmna hmun thlenga tihpun a ni. Tunah chuan voltage chu zero-ah tihhniam tan la, rate a sang chho zel ang.
Magnetization test tih hi a ni.
Tunah chuan voltage tihpun la, excitation current chu CT thlengin saturation point hnaih thlengin enfiah rawh. Voltage leh current chhiar dan record rawh .
hmun engemaw zatah a awm. Curve chu plot la, graph atang chuan VK leh IMG chu evaluate rawh.
 
Turns Ratio Test: (A duh duhin)
He test hi tap zawng zawnga CT a turn ratio enfiah a ni. Circuit connection chu a hnuaia mi ang hian siam tur a ni Fig 6.4. Primary current of 25%rated primary current chu CT primary side-a inject tur a ni a, secondary shorted a ni a, secondary current chu core zawng zawng tan teh & record theih a ni. Limits: Turn’s ratio hmuh chu rated nameplate ratio nen a inmil tur a ni.
 
Primary injection test:
He test hi CT circuit te chu core zah tak nena inzawm tha taka an awm theih nan leh circuit (phase identification) ah mix-up a awm loh nan a ni.The circuit .
Fig 6.4-a kan hmuh angin connection siam tur a ni. Single point grounding chu CT circuit atan verified tur a ni a, he test hi i tan hmain.
Phase pakhat leh Leilung inkara rated primary current 25% chu connected burden zawng zawng hmangin inject rawh. CT circuit point zawng zawngah secondary current teh rawh. Phase dang atan pawh tih tur a ni.