Final trip hmaa transformer stability leh sensitivity test chu power transformer leh current transformer-a parameters chhut leh tehna atana hman tur test pawimawh leh tul tak a ni a, transformer-te nameplate-a data awm angin, test-a thil pawimawh dang chu differential relay chu normal condition-a thawk tur a ni lo tih finfiah a ni bawk a, chutih rualin fault condition-ah a thawk tur a ni. He test neihna tur hian himna atana fimkhurna pawimawh tak tak lak a ngai a, sawiho a ni bawk.
Transformer stability test tih dan kawng hrang hrang a awm a, mahse, he test tih dan tur kan thlan dan pakhat ka sawifiah ang. LV busbar atanga inject la, a result chu transformer protection leh transformer LCP panel ah teh rawh. Mahse inject hmain HV bus bar-ah hian false tripping leh a tul lo taka voltage awm theihna tur ven loh tur a ni a, chu chu kan ngaihtuah a ngai a ni. Differential leh restricted earth faults te tan power transformer a LV leh HV current mamawh te chu chhut la, injection laiin heng parameters te verification atan CT secondary result mamawh te pawh chhut bawk ang che.
LV lam:
Outgoing panel atanga LV busbar kan inject dawn avangin a inmil CT link chu short a ngai a ni. Outgoing leh incomer feeder CB pahnih khar a, power chu transformer LV terminal a thlen theih nan leh VT rack out ngei ngei tur a ni. MCB chu trip circuit atang chuan siam la, generator atanga cable chu LV busbar atanga outgoing feeder eng pawhah connect rawh.
HV lam:
HV side voltage-ah chuan transformer bay-a CT thleng tur a ni a, chuvangin, high-speed Earth Switch chu hawng la & circuit breaker chu khar la, current tan kawng min pe ang a, HV busbar thlenga current kan mamawh lo a, chuvangin CB-in CB direct-a a kal hnua HV current te tak te, earth lam panna a paltlang theih nan Earth switch chu khar vek tur a ni.