Operational impulse test leh lightning shock test te hi high voltage test method hman tlanglawn tak pahnih a ni a, hei hi electrical hmanrua insulation performance endikna atana hman ber a ni. An vai hian transient overvoltages an tel vek a, mahse waveform, purpose leh application scenario-ah hian danglamna lian tak a awm a ni. Hetah hian a danglamna ber chu a awm a;
1. Waveform hrang hrang .
Operational impulse test: 1.1.
Waveform: 250/2500μs (wavefront hun 250μs, a chanve peak hun 2500μs).
Features: Waveform duration a rei a, energy a lian a, simulation operation overvoltage a ni bawk.
Lightning Impulse Test: 1.1.
Waveform: 1.2/50μs (wavefront hun 1.2μs, a chanve peak hun 50μs).
Features: Waveform duration hi a tawi a, a sang a, a sang ber a, lightning overvoltage simulating a ni.
2. Test tum hrang hrang .
Operational impulse test: 1.1.
Power system-a operating overvoltage simulate, switching operation, fault cutting leh transient process dangte ang chi te.
Operating overvoltage condition hnuaia hmanrua te insulation performance endik.
Lightning Impulse Test: 1.1.
Lightning hian hmanrua emaw line emaw a rawn beih hian transient overvoltage siam chhuah chu a simulate thin.
Lightning overvoltage condition hnuaia hmanrua te insulation performance endik.
3. Application scenario hrang hrang .
Operational impulse test: 1.1.
Power system transformer, circuit breaker, cable leh hmanraw dangteah hman ber a ni.
A bik takin operating overvoltage condition hnuaia hmanrua rintlak leh rintlak loh tehna atan a tha hle.
Lightning Impulse Test: 1.1.
Lightning-in a tihchhiat theih tur electrical hmanrua zawng zawng, transmission line, substation hmanrua, etc. te hman theih a ni.
A bik takin lightning environment hnuaia hmanrua te insulation chakna chu ngaihven rawh.
4. Test voltage a danglam .
Operational impulse test: 1.1.
Test voltage hi hmanrua rated voltage aiin a let 2-3 in a sang tlangpui a, a value bik chu hmanrua chi hrang hrang leh standard a zirin a innghat a ni.
Lightning Impulse Test: 1.1.
Test voltage a sang a, a tlangpuiin hmanrua rated voltage aiin a let tam takin a sang a, a value bik chu lightning protection grade leh standard angin a innghat a ni.
5. Test standard hrang hrang .
Operational impulse test: 1.1.
IEC 60060-1, GB/T 16927.1, etc. ang chi standard zawm a ni.
Operating overvoltages simulation leh evaluation-ah hian ngaihtuahna seng rawh.
Lightning Impulse Test: 1.1.
IEC 60060-1, GB/T 16927.1, IEEE C62.41, etc. te zawm a ni.
Lightning overvoltage simulation leh evaluation te chu ngaih pawimawh a ni.