Q: Ka megger hian 500V, 1000V, 2500V, 5000V, leh 10kV a nei a. LV, MV, leh HV tan eng nge ka thlan tur?
A: Voltage tlem lutuk hian insulation a ti stress lo ang. A tam lutuk hian punch-through tichhe thei tak a thlen thei. Table matching chu zawm rawh.
Standard DC Test Voltage thlan dan tur:
| Cable Rated Voltage (U0/U) a ni a, a man pawh a to hle. | Insulation Class a ni | DC Test Voltage atana rawtna siam | Hriselna atana tihkhawtlai (Max) . |
| Voltage hniam (LV) < 0.6/1 kV a ni | Voltage hniam tak a ni | 500V atanga 1000V DC thleng a ni | 1000V DC a ni |
| Voltage (MV) 6/10 atanga 20/35 kV thleng a ni | Voltage lai tak a ni | 2500V emaw 5000V DC emaw a ni thei | 5000V DC a ni |
| Voltage sang (HV) 66 atanga 220 kV+ thleng a ni | Voltage sang tak a ni | 5000V emaw 10,000V DC emaw a ni thei | 10,000V DC a ni |
Engvangin nge IR atan DC hi hman? DC supply hian second engemaw zat hnuah capacitive charging current a la chhunzawm zel lo va, hei hian insulation THROUGH resistive leakage current te tak te (micro-amps) luang chhuak chu teh theih a ni.