AC hipot test nan Transformer (The Tank) test rawh — eng nge a nih leh engtikah nge hman tur tih

 May 27, 2026

 Message pakhat dah la .

 

Q: Test transformer pakhat - chungah bushings awmna metal box lian tak ka hmu em? Engtikah nge reactor stack ai chuan hei hi ka hman ang?

 

A: Ni e - test transformer pangngai chu step-up transformer awlsam tak (220/380V in, 10–300 kV out) a ni. CT, PT, bushing, leh cable tawi (< 25 m).

 

Engtikah nge hman tur:

I test mek a ni...

Capacitance a ni

Test TX em?

Engati nge?

CT (tuna transformer) hmanga siam a ni.

50–200 pF a ni

✅ A tha ber

Tiny load - TX hian awlsam takin a khalh thei

PT (transformer awm thei) 1.1.

100–500 pF a ni

✅ A tha ber

A chhan pawh chutiang bawk chu a ni

Bushing te tak te te

100–500 pF a ni

✅ A tha ber

Resistive load awlsam tak a ni

Cable tawi < 100 m

< 20 nF

✅ A tha

Charging current a hniam tawk

GIS bay (circuit breaker) hmanga siam a ni.

5–50 nF a ni

✅ A pawm theih

Moderate C - Margin nen a OK

5 km a hla power cable a ni

1 μF+

❌ A tha lo

Huge current - FAQ 5 en rawh

Generator stator hmanga siam a ni

1 μF+

❌ A tha lo

Buaina inang chiah

 

A senso tlem ber (thar, 2025):

50 kV / 5 kVA test TX: $8,000–15,000 vel a ni

100 kV / 10 kVA test TX: $20,000–40,000 vel a ni

200 kV / 50 kVA: $50,000+ - mahse a tlem hle; miten he level-ah hian SR-ah an inthlak thin

 

Hmanna hmun: Factory test lab (CT/PT/bushing mfr), switchgear factory, siamthatna dawr te te.

Pro tip: "100 kV / 10 kVA" rating tih hian 100 kV-a resistive load-ah 10 kVA a supply thei tihna a ni. Mahse capacitive cable chhungah chuan voltage dik takah pawh charging current chu 10 kVA - aia tam a ni thei. Chu chu beginners ten test transformer an tihchhiat dan #1 chu a ni.

Inquiry thawn rawh .
Inquiry thawn rawh .