Current transformer (CTs) atana testing standard leh specification te hi power system metering dik leh dik loh, venhimna rintlak leh hmanrua himna tur atana bulpui ber a ni. Anni hian thil pawimawh tak tak, accuracy grades, error limits, testing items, leh test method te an huam a ni.
A dikna tur standard .
CT tehna atana test dik tak standard:
tehna level pangngai (0.1, 0.2, 0.5, 1 level);
A bik takin tehna grade (0.2s, 0.5s grade):
Precision level hniam (3, level 5) .
Test dik taka hman theihna tur CT humhimna atana hman tur CT;
Composite error chu core indicator atan hmangin standard grades chu 5p leh 10p a ni. Entirnan, rated accuracy limit current-ah chuan grade 5p-a composite error chu 5% aia tlem emaw, a tlukpui emaw a ni a, rated primary current-ah chuan current error chu ±1% aia tlem emaw, a tlukpui emaw a ni.
Tuna transformer enfiahna atana hman tur thil leh test standard .
Error Test: Standard current source hmangin proportional current hrang hrang (5%, 20%, 100%) hmang ang che. Tuna error leh phase danglamna chu instrument dik tak hmangin teh la, a inmil accuracy level limits an zawm ngei ngei tur a ni.
Insulation Resistance Test: Ohmmeter hmangin winding leh lei inkar insulation resistance teh la, chutiang bawkin windings te pawh siam bawk ang che. A tlangpuiin, 1000 mΩ aia tam emaw, a tlukpui emaw (a bik takin hmanrua voltage level a zirin) a ngai a ni.
AC withstand Voltage Test: Industrial frequency high voltage (eg, minute 1 chhung 3kV) chu windings-ah apply la, breakdown leh flashover phenomena awm lovin.
DC resistance test of windings: Secondary winding-a resistance value teh la, deviation chu designed value ±10% chhunga awm, windings-te conductivity a awm theih nan teh rawh.