· Test equipment leh capacitor divider (GIS OFF a tha ber-Loading Platform Area) inzawmkhawmna tur hmun dik tak hriat theih nan site survey neih a ni ang.
· HV winding idt chu HV cable box chhungah earth a awm ang.
· Test tan hmain transformer HV cable side oil treatment chu tihfel a nih theih nan leh cable box chu lab-a oil test-a dah a nih leh nih loh enfiah hmasa phawt tur a ni.
· CB (Q0) chu open condition leh Earth switch (Q52) chu closed-a awm a nih theih nan GIS lam a ni.
· Cable box-a gas filled te chu test tur leh a thianghlimna tur enfiah tur quality.
· Testing awmna hmun atanga remote-a termination awmte chu barricad leh warning a ni ang .
· Testing neih mek a nih thu tarlanna tur sign tarlan te chu a awm theih a rinawm.
· Test voltage hman chhung hian IDT / basement room-a luh theihna tur khap a ni ang a, safety precaution atan IDT area termination bulah watchman dah a ni ang.
· HV test adopter dahna GIS bulah AC resonant test set dah a ni ang. HV test set leh GIS HV adopter inkarah span khatah connection siam theih a nih loh chuan HV test lead thlawp turin intermediate temporary support siam a ni ang.
· Test equipment ground zawng zawng chu substation ground system-ah him takin a inzawm vek ang.
· Test equipment atana LV input power awmna tur chu diesel genset a ni ang.
· Test site chhehvelah hian rigid safety barricade, warning sign, leh flashing warning light te dah a ni ang.
· Cable shield leh link box zawng zawng chu SVL tih loh chu an service position-ah a awm ang a, chu chu flash-over a nih chuan a chhiat loh nan short a ni ang.
· HVAC test hi 5KV meggar hmanga conductor leh insulation shield inkara cable insulation resistance tehna atanga tan tur a ni ang.
· Measured value te chu minute khat chhunga tehna zawh hunah record a ni ang.
· Conductor tinte chu insulation resistance test zawh veleh leiah an inzawm ang.
· Test tur cable hmasa ber tihtawp a nih loh nan ground chu tihtawp a ni ang.
· Test lead-a HV output terminal chu Low Corona test lead hmangin cable terminal-ah a inzawm ang.
· Cable HVAC test hi a hun takah phase khat emaw, phase pathum zawng zawng emaw chu client-in a remtih angin leh test adapter awm dan azirin a inzawm khawm thei a ni.
· Test report zawng zawng chu HVAC test tan hmain site-ah a awm vek tur a ni .