Q: Ka 50 kV / 5 kVA test transformer - boss chuan "3 km cable-ah connect mai rawh" a ti. Thil engemaw chu a dik lo niin a hria. Ka dik em?
A: I TI THIN. HEI HI TI LO RAWH. Hei hi transformer tichhe thei #1 beginner mistake a ni.
Buaina #1: Overload lian tak a awm
• Km 3 35 kV cable: C ≈ 0.5 μF a ni. I_charge=50,000 × 314 × 0.5×10−6=7.85 A.
• Power mamawh: 50 kV × 7.85 A=393 kVA.
• I transformer hi 5 kVA a ni. 78× rated power i dil a ni. Winding chu second tlemte chhungin a meikhu chhuak ang.
Buaina #2: Waveform tihdanglam
• Capacitive load → hmahruaitu power factor → transformer core a saturate.
• Output waveform chu peaked - a lo ni ta a, crest factor chu 1.414 atanga 1.6–1.8 ah a kai chho.
• 50 kV RMS test hian 90 kV peak - uncontrolled overstressing a siam thei.
Buaina #3: Voltage regulation a hlawhchham
• No load ah chuan 50 kV i set thin.
• Cable a connect chuan voltage chu 10–20 kV thlengin a tlahniam (transformer hian current a supply thei lo).
• Input chu turn up → TX saturate tam zawk → voltage a tlakchhiat → fuse a puak.
Engtikah nge test transformer hi cable tan a thawh theih?
|
Cable 35 kV ah a awm |
C |
Tunah hian @ 50 kV a ni |
5 kVA TX tan chuan OK? |
|
< 100 m |
< 15 nF |
< 0.24 A |
❌ 2.4× overload a la ni |
|
< 50 m |
< 8 nF |
< 0.12 A |
❌ 1.2× a tam lutuk |
|
< 20 m |
< 3 nF |
< 0.05 A |
✅ Rating chhungah |
Hard rule: ~25 metre aia tawi cable tan chauh test transformer hmang ang che. Eng pawh rei zawk atan chuan series resonant system hmang ang che.
Quick Selection Guide
|
Test i neih chuan... |
Thlang... |
Chhan |
|
CT, PT, bushing, bus bar tawi te te a awm bawk |
Fiahnatransformer hmanga siam a ni |
Simple, man tlawm, power tling |
|
Switchgear / GIS bay 1–2 a awm bawk |
Fiahnatransformer hmanga siam a niemaw SR te tak te emaw a ni thei |
An pahnih hian hna an thawk a ni |
|
Distribution cable < 500 m. a ni |
SR te tak te (30–60 kV) . |
Q-factor power saving a ngai |
|
HV cable > 1 km a ni |
SR (100–300 kV) a ni. |
Viable option chauh a ni |
|
Generator stator hmanga siam a ni |
SR (20–30 kV sang I) a ni. |
Waveform thianghlim, current sang tak |
|
Transformer hmanga test a ni |
SR chu > 100 Hz a ni |
Frequency > rated a ngai a ni |
|
Factory routine (load inang) 1.1. |
TX emaw fixed SR emaw test rawh |
Standardized duhthlan tur |
|
Field test (load hrang hrang) 1.1. |
Modular SR hmanga siam a ni |
Reconfigure theihna tur flexibility a awm bawk |