Cable sei test nan test transformer te tak te hmang ngai suh

 May 27, 2026

 Message pakhat dah la .

 

Q: Ka 50 kV / 5 kVA test transformer - boss chuan "3 km cable-ah connect mai rawh" a ti. Thil engemaw chu a dik lo niin a hria. Ka dik em?

 

A: I TI THIN. HEI HI TI LO RAWH. Hei hi transformer tichhe thei #1 beginner mistake a ni.

 

Buaina #1: Overload lian tak a awm

• Km 3 35 kV cable: C ≈ 0.5 μF a ni. I_charge=50,000 × 314 × 0.5×10−6=7.85 A.

• Power mamawh: 50 kV × 7.85 A=393 kVA.

• I transformer hi 5 kVA a ni. 78× rated power i dil a ni. Winding chu second tlemte chhungin a meikhu chhuak ang.

Buaina #2: Waveform tihdanglam

• Capacitive load → hmahruaitu power factor → transformer core a saturate.

• Output waveform chu peaked - a lo ni ta a, crest factor chu 1.414 atanga 1.6–1.8 ah a kai chho.

• 50 kV RMS test hian 90 kV peak - uncontrolled overstressing a siam thei.

Buaina #3: Voltage regulation a hlawhchham

• No load ah chuan 50 kV i set thin.

• Cable a connect chuan voltage chu 10–20 kV thlengin a tlahniam (transformer hian current a supply thei lo).

• Input chu turn up → TX saturate tam zawk → voltage a tlakchhiat → fuse a puak.

Engtikah nge test transformer hi cable tan a thawh theih?

Cable 35 kV ah a awm

C

Tunah hian @ 50 kV a ni

5 kVA TX tan chuan OK?

< 100 m

< 15 nF

< 0.24 A

❌ 2.4× overload a la ni

< 50 m

< 8 nF

< 0.12 A

❌ 1.2× a tam lutuk

< 20 m

< 3 nF

< 0.05 A

✅ Rating chhungah

Hard rule: ~25 metre aia tawi cable tan chauh test transformer hmang ang che. Eng pawh rei zawk atan chuan series resonant system hmang ang che.

 

Quick Selection Guide

Test i neih chuan...

Thlang...

Chhan

CT, PT, bushing, bus bar tawi te te a awm bawk

Fiahnatransformer hmanga siam a ni

Simple, man tlawm, power tling

Switchgear / GIS bay 1–2 a awm bawk

Fiahnatransformer hmanga siam a niemaw SR te tak te emaw a ni thei

An pahnih hian hna an thawk a ni

Distribution cable < 500 m. a ni

SR te tak te (30–60 kV) .

Q-factor power saving a ngai

HV cable > 1 km a ni

SR (100–300 kV) a ni.

Viable option chauh a ni

Generator stator hmanga siam a ni

SR (20–30 kV sang I) a ni.

Waveform thianghlim, current sang tak

Transformer hmanga test a ni

SR chu > 100 Hz a ni

Frequency > rated a ngai a ni

Factory routine (load inang) 1.1.

TX emaw fixed SR emaw test rawh

Standardized duhthlan tur

Field test (load hrang hrang) 1.1.

Modular SR hmanga siam a ni

Reconfigure theihna tur flexibility a awm bawk

Inquiry thawn rawh .
Inquiry thawn rawh .