Air ingress avanga thianghlimna 95%-ah a tlahniam a nih chuan GIS hian a la thawk thei ang em?

 Jun 30, 2026

 Message pakhat dah la .

 

Q: Air ingress avanga thianghlimna 95%-ah a tlahniam a nih chuan GIS hian a la thawk thei ang em?

A: Energized takin a awm reng ang a, mahse safety margin (arc quenching leh cooling) erawh hlauhawm takin a tlahniam thung.

Thianghlimna hniam avanga hlauhawmna:

❶ Reduced Arc Quenching: Arc tihtawp lai hian air hi SF6 aiin 100x in a chhe zawk. CB hian a titawp thei lo mai thei.

❷ Heat Dissipation: Contamination hian gas density leh cooling ability a tidanglam a, chu chuan overheating a thlen thin.

Standard (IEC 60480) te chu: 1.1.

• Gas thar: 99.9% aia tam emaw, a tlukpui emaw.

• Running Gas: > 97% a ni tur a ni. 95% hnuai lam chu reclamation a ngai.

 

SO2 leh HF level hi engtin nge kan hrilhfiah ang?

Q: Analyzer ah hian SO2 5 ppm a awm tih a lang. Normal result nge internal fault?

A: SO2 hi internal arcing atan "Smoke Alarm" a ni. A hnuaia mi ang hian hrilhfiah rawh:

SO2 Level a ni

Hrilhfiahna

Thiltih

< 1 ppm

Operation pangngai tak a ni.

Routine monitoring neih thin a ni.

1 – 5 ppm a ni

Minor PD emaw switching rit tak emaw a awm thei.

Test interval ti tawi rawh.

5 – 10 ppm a ni

Defect lian tak a awm a.

UHF/Acoustic PD hmangin chhui rawh.

>10 ppm a ni

CRITICAL chhungril lama chhiatna.

Enfiah/thianghlim nghal tur a ni.

Expert Tip: SO2 leh HF pahnih hi a sang a nih chuan tunah hian ACTIVE defect generating acid i nei a ni.

Inquiry thawn rawh .
Inquiry thawn rawh .