Q: Air ingress avanga thianghlimna 95%-ah a tlahniam a nih chuan GIS hian a la thawk thei ang em?
A: Energized takin a awm reng ang a, mahse safety margin (arc quenching leh cooling) erawh hlauhawm takin a tlahniam thung.
Thianghlimna hniam avanga hlauhawmna:
❶ Reduced Arc Quenching: Arc tihtawp lai hian air hi SF6 aiin 100x in a chhe zawk. CB hian a titawp thei lo mai thei.
❷ Heat Dissipation: Contamination hian gas density leh cooling ability a tidanglam a, chu chuan overheating a thlen thin.
Standard (IEC 60480) te chu: 1.1.
• Gas thar: 99.9% aia tam emaw, a tlukpui emaw.
• Running Gas: > 97% a ni tur a ni. 95% hnuai lam chu reclamation a ngai.
SO2 leh HF level hi engtin nge kan hrilhfiah ang?
Q: Analyzer ah hian SO2 5 ppm a awm tih a lang. Normal result nge internal fault?
A: SO2 hi internal arcing atan "Smoke Alarm" a ni. A hnuaia mi ang hian hrilhfiah rawh:
|
SO2 Level a ni |
Hrilhfiahna |
Thiltih |
|
< 1 ppm |
Operation pangngai tak a ni. |
Routine monitoring neih thin a ni. |
|
1 – 5 ppm a ni |
Minor PD emaw switching rit tak emaw a awm thei. |
Test interval ti tawi rawh. |
|
5 – 10 ppm a ni |
Defect lian tak a awm a. |
UHF/Acoustic PD hmangin chhui rawh. |
|
>10 ppm a ni |
CRITICAL chhungril lama chhiatna. |
Enfiah/thianghlim nghal tur a ni. |
Expert Tip: SO2 leh HF pahnih hi a sang a nih chuan tunah hian ACTIVE defect generating acid i nei a ni.