Resistance Tester hman dan .

 May 18, 2023

 Message pakhat dah la .

 

Grounding resistance tester tih hian leia grounding body phum leh lei luang do theihna a kawk a, a tlangpuiin type grounding resistance measuring instrument (a nih loh leh grounding resistance shaker tia koh) hmanga teh a ni tlangpui. Type measuring instrument shape hi ordinary insulating meter nen a inang a, chuvangin custom angin grounding resistance meter an ti bawk. Model hrang hrang nen hian type shaker shaker leh a structure hi a danglam deuh deuh a, mahse a hman dan erawh a bulpui berah chuan a inang vek thung. Type ground resistance tehna hmanrua hian ground detection rod pahnih leh wire pathum a nei a. A hman dan leh a tehna step te chu hetiang hi a ni:
(a) Leilung laka invenna Tester (B) Wire inzawmkhawm (C) Lei rod tehna .
1. Grounding trunk line leh grounding body inkar connection point chu titawp la, a nih loh leh grounding trunk line-a grounding branch line zawng zawng connection point chu disconnect rawh.
2. Leiah 400mm thuk takah grounding rod pahnih dah la, pakhat chu grounding body atanga 40m a hla a ni a, pakhat chu grounding body atanga 20m a hla a ni.
3. Megger chu grounding body bulah hmun zau takah dah la, chutah chuan wiring ti rawh.
(1) Grounding device-a meter-a terminal E leh grounding body E' chu connecting wire hmangin connect rawh.
(2) Connecting wire hmangin meter-a terminal pile C leh grounding rod C’ chu grounding body atanga 40m a hlaah connect tur a ni.
(3) Connection wire hmangin meter-a terminal pile P leh grounding rod p’ chu grounding body atanga 20m a hlaah connect tur a ni.
4. Grounding resistance mamawh angin grounding body tehnaah chuan coarse adjustment knob (a chungah hian adjustable range pathum a awm) chu siamrem rawh.
5. 120 rpm vel speed-in darthlalang chu a rualin vawm rawh. Kut a inthlak danglam chuan kut a centered thlengin fine-tuning dial chu siamrem rawh. Fine-tuning dial-a reading set chu coarse-adjustment positioning multiple nen a puntir a, chu chu test mek grounding body grounding resistance a ni. Entirnan, fine adjustment chhiar chu 0.6 a ni a, coarse adjustment-a resistance positioning multiple chu 10 a ni a, chutah chuan grounding resistance tehna chu 6Ω a ni.
6. Grounding resistance value tehna rintlak a nih theih nan orientation chu thlak leh test leh tur a ni. Grounding body grounding resistance angin measured value engemaw zat average value chu la rawh.

Inquiry thawn rawh .
Inquiry thawn rawh .