Transformer oil a dielectric strength test dan .

 Mar 26, 2024

 Message pakhat dah la .

 

Transformer oil hi electrical transformer-a insulation atana thil pawimawh tak a ni. Transformer tihlum mai bakah electrical component hrang hrangte chu a insulate bawk. Chutiang a nih avang chuan transformer oil-a dielectric strength test fo a pawimawh a, chu chuan beisei angin a thawk thei ang.

Transformer oil dielectric strength test nan hian oil BDV tester kan hmang a, chu chuan oil breakdown voltage a teh a ni. Hei hi BDV test tia hriat a ni. Test-ah hian oil chhunga electrode pahnih inhnim pil inkar gap te tak teah voltage hman a ni. Oil a tlakchhiat thlengin voltage chu a pung zauh zauh a, electrode inkarah chuan arc a lo awm ta a ni. Chutianga a thlenna voltage chu oil breakdown voltage a ni.

BDV test hi oil chhunga bawlhhlawh, tui emaw conductive particle dang emaw awm leh awm loh hriat theihna atana test pawimawh tak a ni. Heng bawlhhlawh te hian oil breakdown voltage a ti tlahniam thei a, chu chuan insulation performance a tihhniam phah thei bawk.

BDV test tih tur chuan hengte hi kan zawm a ni:

1. A hmasa berin, oil sample chu transformer chhunga oil aiawhtu a nih ngei kan mamawh a ni. Container thianghlim leh vawt takah oil sample kan la a. Hetiang dinhmunah hian bawlhhlawh paih loh a pawimawh hle.

2. Oil BDV tester chu a siamtu thupek angin kan set up a. Tester chu a tlangpuiin electrode pahnih, gap- tehna hmanrua, leh voltage source a ni ang.

3. Electrode te chu tester ah kan connect a, oil sample ah kan thun a. Electrode inkar gap hi 2.5 mm ah a awm tlangpui.

4. Oil a chhiat thlengin voltage kan tipung zauh zauh thin. Chutiang a thlenna voltage chu oil sample atan BDV angin a record a ni.

5. Results a inmil leh dik loh enfiah nan test hi vawi thum tal kan ti leh thin.

6. A tawp berah chuan BDV result hi transformer siamtu specification nen kan khaikhin a. BDV chu recommended value aia hniam a nih chuan oil chu thlak emaw, transformer tihfai emaw a ngai thei a, chu chuan contaminants te chu a paih chhuak thei ang.

Transformer oil dielectric strength test hi transformer enkawlna atana thil pawimawh tak a ni. Oil BDV tester hmang hian oil chhunga bawlhhlawh awm apiang chu a insulation performance tihhniam thei tur leh transformer chhiatna a thlen loh nan hmalakna tur dik tak kan hmu thei a ni. Transformer oil test fo hian transformer dam chhung a ti rei thei a, a performance rintlak tak a siam thei bawk.

Inquiry thawn rawh .
Inquiry thawn rawh .