33KV vacuum circuit breakers test dan .

 Nov 28, 2025

 Message pakhat dah la .

 

Vacuum circuit breakers (VCBS) hi medium-voltage power distribution system-ah hian an rintlak a, an enkawlna a hniam a, boruak himna an neih avangin an hmang nasa hle a ni. 33KV VCB hi electrical distribution network tam takah chuan rating tlangpui a ni. System venhimna leh operational safety tih chian nan heng circuit breaker te hi uluk taka test leh maintance a ngai a ni. He thuziak hian circuit breaker analyzer hmanga 33kV vacuum circuit breaker te chu a taka test dan tur a tarlang a ni.

Circuit Breaker Analyzer hi circuit breaker-te performance parameters tehna atana siam, vacuum chi hrang hrang te pawh huam tel, advanced diagnostic test equipment a ni. Contact resistance tehna, dynamic contact resistance (DCR), timing analysis (opening leh closing times), motion analysis, leh dynamic resistance characteristics te ang chi key test a ti thin. He device hman hian a dikna a ti tha a, kut hmanga tihsual a ti tlem a, a hmaa a lo awm emaw, a chhe emaw chhinchhiahna a hriat theih nan a pui bawk.

Circuit breaker analyzer hmanga 33KV VCB hi engtin nge kan test ang?

1. Inbuatsaihna leh himna enfiahna .

- Circuit breaker chu isolated a nih leh nih loh enfiah la, de-a tan hmain tihchak hmasak phawt tur a ni.

- Breaker chu mechanical damage, oil leak (a awm chuan), emaw contamination emaw a awm leh awm loh mitin enfiah rawh.

- Safety ground zawng zawng leh test connection te zawm zawng zawng chu standard relevant te nen a inmil tih finfiah rawh.

- BREAKER-Thil hriat dan tur bik siam dan tur siamtu manual en rawh.

2. Test hmanrua te chu connect rawh.

- CB analyzer-a current sensor leh voltage leads te chu breaker-a main current-carrying terminal-ah nghet takin an dah a.

- Connect control leads te chu analyzer atang hian breaker hawnna leh closing mechanism chu hla tak atangin an thawk thei a.

- Connection zawng zawng chu tight leh insulated vek a nih theih nan accidental contact loh nan enfiah rawh.

3. Contact Resistance Test 100 a awm.

- Analyzer hmangin contact resistance test chu intan tir la, chu chuan main current-carrying contacts te resistance a teh ang.

- Contact resistance hniam chuan electrical connection tha tak a kawk a; 33KV VCB contacts te tan chuan micro-ohms ah hian a awm tlangpui.

- Resistance sang tak tak chuan contact wear emaw pitting emaw a kawk thei a, tihfai emaw thlak emaw a ngai thei.

4. Timing leh Motion Analysis Test .

- Analyzer-a control function hmangin opening leh closing operations tih tur a ni.

- A hawnna leh a khar hunte chu teh rawh; 33KV VCBS hawn hun tlangpui chu millisecond 30 atanga 50 vel a ni.

- Mechanical irregularity awm thei, delays, rebound, emaw sluggish movement te hriat theih nan motion curve siamte chu an zirchiang thin.

5. Dynamic contact resistance (DCR) test 1.1.

- He advanced test hian breaker operation chhungin contact resistance chu a enfiah chhunzawm zel a.

- DCR curve hian contact bounce, timing inconsistencies, emaw partial contact failures ang chi thil hriat theihna a pui a ni.

Inquiry thawn rawh .
Inquiry thawn rawh .