HYPD-800 local defect detector hman dan tur .

 Oct 18, 2024

 Message pakhat dah la .

 

HYPD-800 partial discharge detector hman dan tur hian a bik takin startup preparation, discharge amount correction, test operation leh result analysis te a huam a ni. A hnuaia tarlan te hi a chipchiar taka tarlanna a ni:

1. Inbuatsaihna tan .

· Equipment inspection: Detector chu a thawk tha em tih enfiah la, battery chu a charge kim vek a, display leh button te chu a thawk tha em tih enfiah bawk ang che.

· Time Base Display Mode Setting: Partial discharge signals te enfiah tha zawk turin time base display mode switch chu "Ellipse" mode ah set rawh.

2. Discharge siamthat .

· Correction pulse generator connect rawh: Test voltage i dah hmain figure-a kan hmuh ang hian wire te i connect hnuah discharge amount siam that nan correction pulse generator hmang la.

· Amplifier gain siamrem: Amplifier gain knob chu injected pulse height a remchan theih nan (oscilloscope screen-a 2cm aia sang) siam la, digital meter leh pointer meter-a reading te chu injected known power nena inmil turin siam rawh.

· Fine adjustment knob awmna hmun enkawl: Adjustment hnuah amplifier-a fine adjustment knob awmna chu a danglam thei lo va, calibration lai ang bawkin a awm reng tur a ni.

3. Operation 1000 chu test rawh.

· High-Voltage Test Circuit Power Supply on rawh: zawi zawiin test voltage tihpun la, continuous discharge hmasa ber chu ngaihven la, discharge chuan voltage tlem ber tarlan a pelh chuan voltage chu partial discharge starting voltage a ni.

· Amplifier coarse adjustment knob chu siamrem rawh: Test voltage tarlan hnuaiah, discharge pulse signal i hmuh hnuah amplifier coarse adjustment knob chu display-a discharge pulse height chu 0.2 leh 2cm inkar a nih theih nan siamrem tur a ni.

· Interference pumpelh: Fixed phase interference atan chuan time window device hmangin a veng thei ang. Switch kha khar la, time window pakhat emaw pahnih emaw hmangin potentiometer hmangin ellipse-a highlighted area zau zawng leh awmna tur chu interference pulse atanga hla takah a awm ang.

4. Result thlirletna .

· Read Discharge: Digital Watch Head hmangin discharge a lantir a, a full℃value chu 100 a ni a, he value aia tam hi overload a ni a, a dikna a tichiang thei lo a, gain coarse switch chu low gain gear-ah a flip a ngai a ni.

· Image save rawh: Mouse chu "Save Image" button ah kai la, veilam button kha click la, image chu save rawh. Saved image i chhiar a ngai a nih chuan U disk chu access la, Operation interface kaltlangin image file chu chhiar la, copy rawh.

HYPD-800 partial discharge detector hman dan tur hian link tam tak a huam a, step tin hi operating procedures angin khauh taka kalpui a ngai a ni. He hmanrua hi a remchan dan anga hman a nih chuan, insulation performance testing testing of power equipment efficiency leh accuracy chu a tha thei ang bera siam \\hat theih a ni a, power system kalpui leh enkawlna kawngah \\anpuina chak tak a pe thei a ni.