Transformer pre-commissioning test tih dan tur .

 Nov 20, 2024

 Message pakhat dah la .

 

Transformer pre-commissioning test-ah chuan transformer chu energized a nih hmain service atan a fit em tih a ni. Heng test te hian thil awm thei emaw, dik lohna emaw awm thei te chu a hriat theih nan a pui a, chuvangin transformer hman hmaa tih theih a ni. Hetah hian transformer pre-commissioning tests value bik nei te chu hetiang hi a ni:

Electrical test neih a ni a.

1. Winding Resistance Test: Connection dik tak a awm theih nan winding resistance a teh thin.

- Test voltage: 1-10V DC
- Tolerance: Rated resistance atanga ±1% a ni.

Transformer winding resistance testers model hrang hrang kan nei a, 10A atanga 100A, single phase leh three phase, thlan tur kan nei a.

2. Insulation Resistance Test: Insulation integrity a finfiah.

- Test voltage: 500-1000V DC
- A tlem berah chuan 100 μΩ (Megohms)

BC2030 Insulation Resistance Tester hian transformer test a ti thei a. PI&DAR chu direct-in a display thei bawk.

3. Polarity test: Phase sequence dik tak a nemnghet.

- Test voltage: 100-400V ac

4. Ratio Test: Transformer turns ratio a verify.

- Test voltage: 100-400V ac
- Tolerance: Rated ratio atanga ±0.5% a ni.

 

BBC-Hi Transformer Turn Ratio Tester hian ratio test leh polarity test a ti thei a, transformer victor group direct-in a test thei bawk.

5. NO-Load hloh test: NO-load-a transformer hloh zat tehna.

- Test voltage: Rated voltage 1000 a ni.
- Maximum Loss: A siamtuin a sawi angin

RLS-H transformer capacity &no-Load loss tester hian hei hi a test thei a, test NO-load test a nih chuan voltage regulator nen a inmil a ngai a ni.


Dielectric test 10 a awm bawk.

1. Dielectric Strength Test: Insulation chakna a finfiah.

- Test voltage: voltage rated 2-3 (50/60 Hz) a ni.
- Test hun chhung: Darkar 1

Kan AC/DC Hipot Tester hian transformer atan dielectric strenght test a ti thei a, test mamawh dan azirin suitabe model chu i choos thei bawk.


2. Partial discharge test: Insulation defects a hmuchhuak.

- Test voltage: voltage rated 1.5-2 a ni.
- Frequency: 50/60 Hz .

Non-PD test system hian offline PD test chu transformer atan a ti thei a ni.

3. AC voltage withstand test: Insulation withstand capability a finfiah.

- Test voltage: voltage rated 2-3 (50/60 Hz) a ni.
- Test hun chhung: Darkar 1
Kan AC/DC Hipot Tester hian transformer atan dielectric strenght test a ti thei a, test mamawh dan azirin suitabe model chu i choos thei bawk.


Transformer oil test te pawh a awm bawk.

1. Oil dielectric chakna test: Oil insulation chakna tehna.

- Test voltage: 30-50 kV a ni.
- Dielectric chakna tlem ber: 30 kV

Kan jyy-Hi Oil BDV tester hian single cup a nei a, voltage pawh 80kv thleng a ni.


2. Oil Moisture Content Test: Oil tui awm zat tehna.

- A tui awm zat a tam ber: 2% (a rit zawng atanga chhut)

YWS-2 oil moisture content tester hian accureny leh performance sang tak a nei a, hman a awlsam a, portable a ni bawk.


3. Oil Acidity Test: Oil acidity tehna.

- Acidity sang ber: 0.5 mg KOH/g

Transformer oil acid value test nan YSZ-H oil acidity tester kan nei a. A hman a awlsam a, performance sang tak a nei bawk.

Taksa leh hmuh theiha test .

1. Mit enfiahna: Taksa lama chhiatna emaw, chhiatna emaw a awm leh awm loh a enfiah thin.
2. Tightness test: Electrical connection te a verify thin.
3. Transformer Oil Level Check: Oil level tling a awm leh awm loh enfiah.
4. Cooling System Check: Cooling system hnathawh dan a dik leh dik loh enfiah.


Control leh Protection System test 1000 a awm bawk.

1. Protection Relay Test: Protection relay hnathawh dan a dik leh dik loh enfiah.
2. Control Circuit Test: Tests control circuit hnathawh dan tur.
3. Alarm leh Interlock Test: Alarm leh interlock functionality a verify.

Hriselna atana test .

1. Leilung fault test: Leilung fault laka invenna a dik leh dik loh enfiah. DER2571 Earth Resistance Tester hmangin check theih a ni a, Earth Fault Detector pawh i hmang thei bawk.


2. Lightning Arrestor Test: Lightning Arrestor hnathawh dan a test. FC-2GB lightning components tester pawh hman theih a ni.

3. Grounding test: Grounding system integrity a dik leh dik loh enfiah.

Standards zawm dan .

1. IEC 60076-1 (Power Transformers) a awm a.
2. IEC 60076-2 (temperature a sang)
3. IEC 60076-3 (insulation level) a ni.
4. IEEE C57.12.00 (liquid-Transformer-a tui pek chhuah, power, leh regulating transformer-a immersed-a hman tur standard)
5. ANSI/IEEE C57.13 (instrument transformer atana hman tur standard mamawh)

Pre-Commissioning checklist a ni.

1. A siamtu documentation chu enfiah leh rawh.
2. Electrical connection te enfiah thin ang che.
3. Test control leh venhimna system te.
4. Visual inspection tih tur.
5. Hriselna atana test neih thin.