Transformer a chhiat loh nan solution chu transformer-a insulating oil hman thin chu test reng a ni. Oil hian coolant leh dielectric material angin hna a thawk a, a dinhmun hi transformer chu a tha thei ang bera a thawh theih nan a pawimawh hle. Transformer oil test pawimawh ber pakhat chu break down voltage (BDV) test a ni. BDV test hian transformer oil sample-a insulation a chhiatna voltage a teh a, chu chuan a hman tumna atan a hlawk lo hle. Test neih chhung hian oil sample pakhat chu voltage a sang chho zel a, spark jumps record a ni bawk. Voltage reading hi a tlangpuiin kilovolt (KV) ah an sawi thin. Transformer oil test hi engtin nge kan tih ang?
Oil sample lak dan: 1.1.
• Glass bawm thianghlim leh vawt tak hman tur a ni. Container lian leh te chu test cell aiin a let thum talin a lian tur a ni. (Container litre 1 vel a tling) a tawk)
• Sampling lai hian glass container chu oil tlem te te in silfai la, drain rawh.
• Container chu a hmin hma loh chuan oil hmangin hriak la.
• Container chhungah free air space dah loh tur.
• Container chhungah boruak bubble dah loh tur a ni.
• Sampled container chu cork emaw, nonreactive material dang emaw hmangin airtight khar tur a ni.
• (Duh zawk thlang). Oil chu hmun hla zawka phurh chhuah a nih chuan, oil chu hmun thianghlim leh vawt takah dahin, fimkhur takin phurh chhuah a nih theih nan enfiah tur a ni.
• Test cell-a oil i fill hmain, air bubble siam lovin container chu zawi zawiin a tithinrim ang.
• Test cell bang chu oil tlem hmangin silfai la, a tui chhuah tir rawh.
• Test cell a electrode te chu a fai em tih enfiah tur.
• Oil sample chu a luang chhuak thlengin fill up la, air bubble siam lovin test cell chhungah dah rawh.
• 5 min tal test tan suh. Test sample (oil) a fill hnuah.
Voltage test chu a tichhia a:
• Oil sampling hi sampling instruction-a tarlan procedure angin tih tur a ni.
• BDV test hi test cell chhunga sample oil filling atanga minute 5 tal atanga tan tur a ni.
• Electrode inkar gap chu 2.5mm-ah a awm reng theih nan enfiah rawh.
• Electrode te chu a fai em tih enfiah tur.
• Second khata 2kV a test voltage a san dan rate.
• Test inkar minute 3 - 4 aia tlem lo chu sample khat atan vawi 5 atanga vawi 6 BDV test neih thin ang che.
• Test inkar ah test sample stirring tih a nih leh nih loh enfiah tur a ni.
• Test result record la, test result average chu hmu la, test sample breakdown voltage hmuh theih a ni ang. (Odd value te chu ngaihthah rawh)