SF6 gas circuit breaker test tih dan tur .

 Mar 19, 2025

 Message pakhat dah la .

 

SF6 (Sulfur hexafluoride) circuit breaker hi high-voltage electrical switchgear device a ni a, SF6 gas chu a insulating leh arc atan a hmang a, quenching medium a ni a, medium to high-voltage power transmission leh distribution system-ah hman a ni tlangpui.
400-400
1. 𝗖𝗼𝗻𝘁𝗮𝗰𝘁 𝗥𝗲𝘀𝗶𝘀𝘁𝗮𝗻𝗰𝗲 𝗧𝗲𝘀𝘁
𝐏𝐮𝐫𝐩𝐨𝐬𝐞:
Current flow tha tak neih theihna tur leh overheating awm lohna turin main contacts te resistance a teh thin.
𝐏𝐫𝐨𝐜𝐞𝐝𝐮𝐫𝐞:
1.Micro-ohmmeter (Mjolner 200 tester) hmang rawh.
2. DC current (a tlangpuiin 100a aia tam) hmang rawh.
3. Voltage drop teh la, R=V/I hmangin resistance chhut rawh.
𝗔𝗰𝗰𝗲𝗽𝘁𝗮𝗻𝗰𝗲 𝗖𝗿𝗶𝘁𝗲𝗿𝗶𝗮:
Resistance sang hian wear, contamination, emaw connection tha lo a kawk a ni.

2.𝗧𝗶𝗺𝗶𝗻𝗴 𝗧𝗲𝘀𝘁 (𝗢𝗽𝗲𝗿𝗮𝘁𝗶𝗼𝗻𝗮𝗹 𝗧𝗲𝘀𝘁)
𝐏𝐮𝐫𝐩𝐨𝐬𝐞:
Breaker chu hawn leh khar hun bituk chhunga a thawh theih nan a enkawl.
𝐏𝐫𝐨𝐜𝐞𝐝𝐮𝐫𝐞:
1. Circuit breaker analyzer hmang rawh.
2. A tehna: 1.1.
Opening hun chhung .
Inkharkhip hun .
Bounce hun hman dan .
3. A siamtu specification nen results te khaikhin rawh.
𝗔𝗰𝗰𝗲𝗽𝘁𝗮𝗻𝗰𝗲 𝗖𝗿𝗶𝘁𝗲𝗿𝗶𝗮:
A hawn hun chhung: 20–60 ms
A khar hun chhung: 30–80 ms
Phase hrang hrang inkara danglamna tur .
Minimal takin awm rawh.
3.𝗦𝗙₆ 𝗚𝗮𝘀 𝗟𝗲𝗮𝗸𝗮𝗴𝗲 𝗧𝗲𝘀𝘁
𝐏𝐮𝐫𝐩𝐨𝐬𝐞:
Gas leak te chu insulation dik tak a nih theih nan a detect a, arc-Qualquenching performance a nei bawk.
𝐏𝐫𝐨𝐜𝐞𝐝𝐮𝐫𝐞:
1. SF3 gas leak detector emaw thermal imaging camera emaw hmang la.
2. Seal, flanges leh gas compartment vel scan tur a ni.
𝗔𝗰𝗰𝗲𝗽𝘁𝗮𝗻𝗰𝗲 𝗖𝗿𝗶𝘁𝗲𝗿𝗶𝗮:
SF₆ leakage chu kum khatah < 0.5% a ni tur a ni (IEC 62271-203 angin).

4.𝗦𝗙₆ 𝗚𝗮𝘀 𝗣𝘂𝗿𝗶𝘁𝘆 𝗧𝗲𝘀𝘁
𝐏𝐮𝐫𝐩𝐨𝐬𝐞:
Insulation quality a awm theih nan SF₆ gas concentration a teh thin.
𝐏𝐫𝐨𝐜𝐞𝐝𝐮𝐫𝐞
1. SF3 gas analyzer hmang rawh.
2. SF₆ thianghlimna percentage teh rawh.
𝗔𝗰𝗰𝗲𝗽𝘁𝗮𝗻𝗰𝗲 𝗖𝗿𝗶𝘁𝗲𝗿𝗶𝗮:
SF₆ thianghlimna chu 99.5% aia tam emaw, a tlukpui emaw a ni tur a ni.
Lower purity hian gas a mamawh a ni .
A replenishment a ni.

5.𝗦𝗙₆ 𝗗𝗲𝘄 𝗣𝗼𝗶𝗻𝘁 𝗧𝗲𝘀𝘁 (𝗠𝗼𝗶𝘀𝘁𝘂𝗿𝗲 𝗧𝗲𝘀𝘁)
x-ah hian moisture contamination awm leh awm loh enfiah la, insulation performance a nghawng thei.
𝐏𝐫𝐨𝐜𝐞𝐝𝐮𝐫𝐞
1. SF3 dew point meter hmang rawh.
2. Dew point chu degree-in teh rawh .
𝗔𝗰𝗰𝗲𝗽𝘁𝗮𝗻𝗰𝗲 𝗖𝗿𝗶𝘁𝗲𝗿𝗶𝗮:
Dew point chu operating-ah -40℃aia tlem emaw, a tlukpui emaw a ni.
delh.
moisture tamna a tam avangin .
Insulation a hlawhchham.
6.𝗗𝘆𝗻𝗮𝗺𝗶𝗰 𝗖𝗼𝗻𝘁𝗮𝗰𝘁 𝗥𝗲𝘀𝗶𝘀𝘁𝗮𝗻𝗰𝗲 𝗠𝗲𝗮𝘀𝘂𝗿𝗲𝗺𝗲𝗻𝘁 (𝗗𝗖𝗥𝗠)
𝐏𝐮𝐫𝐩𝐨𝐬𝐞.
Breaker hnathawh laiin resistance inthlak danglamna a teh thin.
Contact wear leh SF₆ nozzle condition a hmuchhuak.
𝐏𝐫𝐨𝐜𝐞𝐝𝐮𝐫𝐞
1. DCRM test set hmang rawh.
2. Resistance 1000 chhunga resistance teh rawh.
3. Wear leh erosion awm leh awm loh thlirlet.
𝗔𝗰𝗰𝗲𝗽𝘁𝗮𝗻𝗰𝗲 𝗖𝗿𝗶𝘁𝗲𝗿𝗶𝗮:
Resistance curve chu a smooth tur a ni.
Resistance sang tak tak peaks te hian .
Arcing contact chhia a awm.