Current transformer atana primary injection test tih dan tur .

 Sep 29, 2024

 Message pakhat dah la .

 

Tuna transformer awm mekte integrity tihdikna atan hian primary injection test hi a pawimawh hle. Heng test te hian current transformer te hian current an teh dik em tih leh an thawk tha em tih hriat theihna a siam a ni. He thuziak ah hian tuna transformer awm mekte tana primary injection test tih dan tur kan sawi dawn a ni.

He test hi CT circuit te chu core zahawm tak tak te nen a inzawm tha em tih leh circuit (phase identification) ah mix up a awm loh nan a ni.The circuit .
Connection siam a ni ang. Single point grounding chu CT circuit atan verified tur a ni a, he test hi i tan hmain. Phase pakhat leh Leilung inkarah hian rated burden zawng zawng hmangin rated primary current 25% inject tur a ni. CT circuit point zawng zawngah secondary current teh rawh. Phase dang atan pawh tih tur a ni.

Primary injection test hian tuna transformer hnathawh dan a teh a, chutah chuan saturation, ratio, leh phase shift te pawh a tel a ni. Test-naah hian hmanraw bik a ngai a, chu chu a man a to hle a, hman dik theih nan experience sang tak a mamawh a ni.

Primary injection test hlawhtling tak neih theih nan a hnuaia step te hi a pawimawh hle:

Step 1: Test hmanrua te chu set up rawh .

Test equipment hi primary current injector leh secondary winding output record theihna tur tehna hmanrua tling tak a ni. Connection zawng zawng chu a tight vek a, accident a awm loh nan insulation tha tawk tak a awm theih nan enfiah tur a ni. Test neih chhunga accidental activation awm loh nan test equipment te chu interlock rawh.

Step 2: CT chu test atan buatsaih rawh .

CT-a secondary cable chu system atang chuan phelh la, secondary winding chu leiah short rawh. CT chu nominal secondary current rating-ah dah rawh. Primary winding chu current injector nen a inmil em tih enfiah tur a ni. Primary winding polarity a dik leh dik loh finfiah rawh.

Step 3: Test chu ti rawh .

Primary current injector chu activate la, current waveform chu sinusoidal waveform hnaih a nih leh nih loh enfiah rawh. Zawi zawiin primary current chu rated full-load current-ah tihpun rawh. Primary current tak tak leh secondary current output tehna chu record rawh.

Step 4: Test result te chu thlirlet rawh .

Primary current tak tak leh secondary current output tehna chu khaikhin rawh. Tuna transformer ratio awm chu chhut la, an inkar percentage error chu chhut rawh. Phase shift a awm leh awm loh enfiah la, siamtuin a huam chin bituk chhunga a awm leh awm loh enfiah bawk ang che.

Inquiry thawn rawh .
Inquiry thawn rawh .