Tuna transformer awm mekte integrity tihdikna atan hian primary injection test hi a pawimawh hle. Heng test te hian current transformer te hian current an teh dik em tih leh an thawk tha em tih hriat theihna a siam a ni. He thuziak ah hian tuna transformer awm mekte tana primary injection test tih dan tur kan sawi dawn a ni.
Primary injection test hian tuna transformer hnathawh dan a teh a, chutah chuan saturation, ratio, leh phase shift te pawh a tel a ni. Test-naah hian hmanraw bik a ngai a, chu chu a man a to hle a, hman dik theih nan experience sang tak a mamawh a ni.
Primary injection test hlawhtling tak neih theih nan a hnuaia step te hi a pawimawh hle:
Step 1: Test hmanrua te chu set up rawh .
Test equipment hi primary current injector leh secondary winding output record theihna tur tehna hmanrua tling tak a ni. Connection zawng zawng chu a tight vek a, accident a awm loh nan insulation tha tawk tak a awm theih nan enfiah tur a ni. Test neih chhunga accidental activation awm loh nan test equipment te chu interlock rawh.
Step 2: CT chu test atan buatsaih rawh .
CT-a secondary cable chu system atang chuan phelh la, secondary winding chu leiah short rawh. CT chu nominal secondary current rating-ah dah rawh. Primary winding chu current injector nen a inmil em tih enfiah tur a ni. Primary winding polarity a dik leh dik loh finfiah rawh.
Step 3: Test chu ti rawh .
Primary current injector chu activate la, current waveform chu sinusoidal waveform hnaih a nih leh nih loh enfiah rawh. Zawi zawiin primary current chu rated full-load current-ah tihpun rawh. Primary current tak tak leh secondary current output tehna chu record rawh.
Step 4: Test result te chu thlirlet rawh .
Primary current tak tak leh secondary current output tehna chu khaikhin rawh. Tuna transformer ratio awm chu chhut la, an inkar percentage error chu chhut rawh. Phase shift a awm leh awm loh enfiah la, siamtuin a huam chin bituk chhunga a awm leh awm loh enfiah bawk ang che.