Transformer atana insulation resistance/polarization index test tih dan tur.

 Nov 11, 2024

 Message pakhat dah la .

 

Insulation resistance leh polarization index test te hi transformer insulation dinhmun hriat theihna atana diagnostic tool pawimawh tak a ni. Heng test te hi insulation chungchanga harsatna awm thei te hriatchhuah nan hman a ni a, hei hian catastrophic system a chhiat loh nan leh transformer dam chhung a ti rei thei a ni.

Insulation resistance leh polarization index test chu 100 hnuaiah neih a ni ang.
A hnuaia connection-ah hian test voltage (5kv DC) hmang la, readings te chu note down rawh .
pahnih winding transformer .
HV – Leilung .
LV – Leilung .
HV-lv .
Three winding transformer .
HV – Leilung .
LV1 –Lei .
LV2 –Lei .
HV -LV1.
HV -LV2.
lv1 -LV2.
Insulation resistance tehna chu second 15 atanga minute 1 thleng 15 15-second interval hmangin an ti a, chuta tang chuan minute sawm atanga minute sawm thleng an ti leh thin. Minute 10-a value hmuh zat chu minute 1-a value hmanga then chuan polarization index a pe a ni.

Transformer-a insulation resistance leh polarization index test tih hi preventive maintenance atana thil pawimawh tak a ni. Heng test te hian insulation chungchanga harsatna awm thei te chu a hriat theih nan leh a hlawhchhamna man to tak tak te a veng thei a ni. High-voltage system hmanga hnathawh hunah himna kalphung dik tak zawm a pawimawh a, DOU i neih chuan professional thiam tak i zawh fo a pawimawh bawk.

Inquiry thawn rawh .