GIS-a gaseous leh solid insulation chu AC voltage withstand test-ah dah a ngai a ni. GIS installation hrang hranga capacitance variation lian tak tak avang hian variable frequency HI-POT test unit hman a ni fo thin. Variable frequency high potential unit hian standard-a tarlan magnitudes leh duration-ah voltage hmanna tur low frequency (30 Hz to 300 Hz) a siam thei a ni. Hemi one{{6}minute low- frequency voltage withstand verification hi rated low-frequency withstand voltage siamtu factory-a tih 80%-ah tih a ni. Conditioning voltage application sequence, magnitude leh durations siamtuin a tihfel tur chu defined one{{11}minute withstand test hmaah a awm tur a ni. Conditioning verification hian a tum ber chu particle te te, a awm chuan electric field intensity hniam tak tak, particle trap ang chi te chu khalh tir a ni. Heng high voltage verifications te hian a tum ber chu gas-insulated substation elements te chu transport an damchhuak tawh em tih te, an inzawm dik em tih te, chambers chhunga extraneous material awm lo te, GIS installation te hian test voltage an tuar thei tih te enfiah a ni. Conditioning voltage application sequence leh one-minute low-frequency voltage withstand verification chu GIS installation install a nih hnuah tihfel a ngai a, gas chambers chu a siamtuin a rawt nominally rated fill density leh gas moisture content leh purity te chu defined limits chhungah a awm tih enfiah a ni tawh a ni.
AC voltage withstand ruahmanna leh hman dan tur .
GIS installation check mek chu GIS hmanrua hman tawh nen a inzawm chuan in-service part chu test tawh part atang chuan electrically isolated a ngai a ni. Chuti chung pawh chuan, test voltage chu IN-service voltage hmangin phase atanga 180℃out of phase a ni thei a, chu chuan disconnect switch-a open gap chu a pholang thei a, isolation atan hman a ni thei a, chu chu voltage tam zawk, a tuar theih loh tur a ni. Chuvangin, grounds tling nei isolated section chu in-service GIS leh GIS check tur inkarah hman a ngai a ni. Hei hian test voltage hian electrical system-a service tihbuai a siam thei lo va, service voltage hian test-na hmanruaah chhiatna nasa tak a thlen thei a, test staff-te tan hlauhawmna a siam thei bawk. Test-na hmanrua te electrical loading restriction avang hian open disconnects hmanga GIS section isolate a, section tin a hrana test a ngai thei. Chutiang ti thei tur chuan GIS hmanrua thenkhat chu test voltage pakhat aia tam hman a ngai mai thei. A parts endik lohte chu earthed a ngai a ni. GIS hmanrua thenkhat isolating chuan field testing atanga hlawkna dang a pe thei a, chutiang field test chu a ngai lo nachungin, disconnecting switch thenkhat open gap chu a mamawh a ni. Chu bakah, disruptive discharge awmna hmun awlsam zawk nan emaw, disruptive discharge laiin energy discharge theih tur tihtlem nan emaw GIS section isolate a ngai thei bawk. Test voltage source chu phase enfiah tur hmun remchang apiangah a inzawm thei a ni.