IEC standard hmanga low voltage(LV) cable awm leh awm loh AC hipot test engtin nge kan tih ang?

 Aug 27, 2025

 Message pakhat dah la .

 

IEC standard hmanga low voltage(LV) cable awm leh awm loh AC hipot test engtin nge kan tih ang?

 

Low-voltage cable te hi Cable factory-in AC Hipot test a neih hian IEC standards (IEC 60502 series ang chi) a zirin cable type leh rated voltage ang chi parameter hmanga hriat a ngai a ni.

1. Test voltage:

Cable-a rated voltage (U0) atanga chhut chuan factory test voltage chu a tlangpuiin U0 aiin a let 3.5 in a sang zawk (entir nan, rated voltage 0.6/1 kV, U0=0.6 kV nei tan chuan, test voltage chu 2.1 kV a ni). He value hi factory siam chhuah lai khan insulation performance verify turin preventive test standard aiin a sang zawk a ni.

 

2. Test hun chhung:

China GB 50150-a LV cable-a AC hipot test-a preventive test hian minute 60 chhung atan U0 voltage vawi 2.5 a hmang a, chutih laiin IEC standard hmangin, LV cable factory tan chuan short-Term high-voltage verification (minute 15 chhung U0 vawi 3.5) chu a dah pawimawh zawk a ni.

 

3. Test frequency:

Industrial frequency (50/60Hz) emaw, variable frequency 20 atanga 300Hz thlenga power supply emaw. Industrial frequency hman hmasak ber tur. Thil hmanrua a tlem chuan variable frequency hmang la, mahse waveform quality chu enfiah rawh.

 