AC Hipot test neih laiin flashover leh breakdown hi engtin nge kan thliar hrang ang?

 May 18, 2026

 Message pakhat dah la .

 

Test lai hian spark lian tak ka hmu a, relay chu a trip ta a. Flashover nge breakdown - a ni em a, engtin nge a danglamna ka hriat theih ang?

 

Flashover (external surface discharge) leh breakdown (internal puncture) thliar hran hi a pawimawh hle a, a chhan chu corrective action hi a danglam vek a ni.

 

Thuhmahruai (IEC 60060-1):

• Flashover: Insulator SURFACE atanga discharge (pawn lam - insulation chu a la awm reng thei).

• Breakdown / Puncture: Solid emaw liquid emaw insulation hmanga paih chhuah (internal - permanent damage).

 

Hmuhdan

Flashover (Pawn lam atanga chhuak) .

Inthenna (Internal) 1.1.

Discharge kawng hmuh theih

Bushing surface emaw air gap emaw zawh zawng zawngah

Insulation hmangin - chu a lang lo mai thei

Ri

"Crack" ri nasa tak, nalh tak (air ionization) .

Duller "thump" (oil/paper hmanga) .

Arc awmna hmun a ni

Live terminal leh lei inkar ah hmuh tur a awm

Chhunglam; surface path hmuh tur a awm lo

Post-test IR

Normal (insulation a awm lo) .

A tlahniam nasa hle (compromised) .

Post-test Tanδ tih a ni

Normal emaw, a sang deuh emaw

Dramatic takin a pung ta a ni

Post-test DGA tih a ni

Hrilhfiahna a awm lo

C2H2, H2 chu oil hmanga puncture arcs a nih chuan

 

Thutlukna siamna thing:

1. Discharge path chu lei chung lamah a lang em?

→ YES=flashover → fai, vawt, re-test.

→ NO=hi chhungril lam a ni thei. IR → a hniam=breakdown a nih chuan teh rawh.

2. Discharge chu voltage inangah a repetitive em?

→ YES=chhungril lama chhiatna (a awm leh ang).

→ NO=random surface flashover (contamination) a awm lo.

 

Practical rule pawimawh tak:

• Flashover hi test setup failure a ni a, equipment failure a ni lo.

• Internal breakdown IS hmanrua chhia - siamthat emaw thlak emaw a ni.

• Document fo thin: discharge laiin voltage, khaw lum leh khaw vawt, lei chung bawlhhlawh.

Inquiry thawn rawh .
Inquiry thawn rawh .