short-Circuit impedance chu short-circuit test laiin circuit impedance a awm ang.
Transformer pakhat short-circuit impedance, impedance voltage tia hriat bawk hi transformer parameter pawimawh tak a ni a,drated load a kal laiin transformer ngeia impedance voltage drop a lantir a ni. A bik taka chhut dan chu hetiang hi a ni: Test steps: Pakhatnaah chuan, short-Circuit transformer secondary side winding. Tichuan, primary side winding-ah chuan rated frequency-a AC voltage an dah a. Zawi zawiin primary current chu rated value a thlen thlengin voltage chu tihpun a ni. Hetih lai hian primary side winding-a voltage UZ hnawih chu record rawh.
Calculation Formula: A tawp berah chuan, recorded voltage UZ leh transformer-a rated voltage UN angin short-circuit impedance proportion chu chhut theih a ni.Forula chu UZ%=UZ/Un × 100% a ni. He percentage hi transformer-a short-circuit impedance a ni.
Chu bakah, short-circuit impedance test hian short-circuit current in operation a nghawng hnuah transformer dinhmun a enfiah mai bakah transformer chhunga a chhunga structure awm chu a dik em tih a teh thei bawk a, chu chu winding chu a deformed nge a displaced tih te a ni.
A tlangpuiin, short-circuit impedance test leh calculation hmang hian transformer hnathawh dan hriatthiamna zau tak i nei thei a, chu chu power system-a a hnathawh nghet theih nan a ni.