Q: Cable 220 kV, km 8 a sei test ka mamawh. Eng SR rating nge ka mamawh?
A: 7-step sizing procedure: test mamawh tur ruat → C chhut → L chhut → f_res chhut → ratings verify → iterate → finalize.
Step-by-step - 220 kV cable, km 8:
1. IEC 60840: V_test=2.0 × 127 kV=254 kV. Hun chhung 60 min.
2. C ≈ 8 km × 0.2 μF/km=1.6 μF a ni.
3. 3× 100 kV/2 A reactors parallel-a awmte han ngaihtuah teh: L=26.7 H, f=24.4 Hz.
4. Current 254 kV: I=V × 2πf × C=6.9 A. Mahse 3×2A → 6A total → OK LO.
5. Reactor 3× 100 kV/4 A thlenga tihchangtlun: a vaiin I=12 A → OK. P_in=254×6.9/35=50 kW a ni.
6. A rih zawng zawng: 3×450 kg + 200 + 150 + 100=~1,800 kg.
Scenario tlanglawn tak takte tana sizing summary:
|
Scenario a ni |
V_test (kV) a ni. |
C (μF) |
f (Hz) a ni. |
System rawtna siam |
|
33 kV cable, km 3 a thui a ni |
48 |
0.6 |
45 |
60 kV/2A ×1, 5 kW a ni |
|
110 kV cable, km 5 a thui a ni |
160 |
1.0 |
24 |
200 kV/4A ×2, 20 kW a ni |
|
220 kV cable, 8 km |
254 |
1.6 |
24 |
300 kV/4A ×3, 50 kW a ni |
|
400 kV cable, km 5 a thui a ni |
330 |
1.0 |
48 |
400 kV/2A ×2, 25 kW a ni |
|
GIS 245 kV, bay 10 a ni |
230 |
0.05 |
80 |
300 kV/1A ×2, 5 kW a ni |
|
Generator 100 MVA a ni |
28 |
2.5 |
45 |
30 kV/5A, 10 kW a ni |
Hriat nawn tirna pawimawh tak tak:
• Reactor voltage rating-ah +20% margin. +30% margin chu current rating-ah a awm.
• P_in > 100 kW a nih chuan sectional testing (standard tam zawkin a phal) ngaihtuah rawh.
• Q tak tak chu chhut aiin a hniam thei - conservative planning hian field failure a veng thei.