AC Hipot test atana test voltage thlan dan tur chu eng nge ni?
Test voltage hi hmanrua rated insulation level (Um, BIL) atanga teh a ni a, product standard hman tur - universal voltage pakhat chauh a awm lo.
Equipment chi hrang hranga voltage thlan dan:
|
Hmanrua |
Nihphung pangngai |
Voltage test a ni |
Rei zawng |
|
Power Transformer (Um 72.5 kV aia tlem emaw, a tlukpui emaw) |
IEC 60076-3 hmanga tih a ni |
1.7 × Um / √3 (induced) + PD a ni |
30 s test-naah + 5 min Um/√3-ah |
|
Power Transformer (Um > 72.5 kV) hmanga siam a ni. |
IEC 60076-3 hmanga tih a ni |
1.7 × Um / √3 (hun rei lote-induced) . |
60 s |
|
A chhuahna tur Transformer a ni |
IEC 60076-11 ah a awm |
2.0 × rated voltage a ni |
60 s |
|
Power Cable (MV) hmanga siam theih a ni. |
IEC 60502-2 ah a awm |
2.5 × U₀ |
30 min (pawm) / 60 min (maint) a ni ang. |
|
Power Cable (HV) hmanga siam theih a ni. |
IEC 60840 a ni |
2.0 × U₀ |
60 min |
|
GIS / Switchgear hmanga siam a ni |
IEC 62271-1 hmanga tih a ni |
1.2 × Um |
60 s |
|
Bushing a ni |
IEC 60137 a ni |
1.2 × Um (PF test) a ni. |
60 s |
|
CT / VT hmanga tih a ni |
IEC 61869-1 ah a awm |
1.3–1.5 × Um/√3 (induced) a ni. |
60 s |
Field kaihhruaina hmantlak tak:
• Nameplate (Um, BIL tih ziak) chu en fo ang che.
• Kum upa tawh hmanrua field test nan voltage 80% tihhniam (Cable tan IEEE 400.2).
• Nameplate BIL aia tam ngai suh.
• Voltage - transformer vs. cable voltage thlan hmain product standard chu class khat tan a danglam tih finfiah hmasa phawt ang che.