DGA result hi engtin nge an hrilhfiah thin — key ratio methods te chu engte nge ni?

 May 15, 2026

 Message pakhat dah la .

 

DGA report ka nei a, gas pasarih concentration a awm. Engtin nge heng number te hi diagnosis ah ka chantir theih ang?

 

A: International-a hriat hlawh ratio method pathum hmangin gas concentration chu fault type diagnosis-ah an chantir a ni. Cross-verification atan pathum hmang vek rawh.

Thiltih dan 1: IEC 60599 / IEEE C57.104 Duval Triangle (a hman tam ber) .

Zone a ni

Fault chi hrang hrang

Gas Signature pangngai tak a ni

PD a ni

Partial discharge a ni

H2 dominant, CH4 te tak te

D1

Energy chhuahna hniam-(sparking) .

C2H2 > HC zawng zawng atanga 4% a ni

D2

Energy chhuahna sang-(arcing) .

C2H2 + C2H4 dominant a ni

T1

Thermal fault < 300℃a ni

CH4 + C2H3 a thunun ber

T2

Thermal fault 300℃–700℃

C2H4 > CH4 a ni

T3

Thermal fault > 700℃a ni

C2H4 + H2 a sang

DT

Thermal + electrical (mixed) hmanga siam a ni.

Mixed pattern a ni

Thiltih dan 2: IEEE C57.104 Gas awm zat tihtlem dan

Gas a ni

Thil awmdan 1 (Normal) 1.1.

Condition 2 (Fimkhur tur) 1.1.

Thil awmdan 3 (Alert) 1.1.

Condition 4 (Risk sang tak) 1.1.

H₂

100 ppm aia tlem emaw, a tlukpui emaw a ni

101–200 ppm inkar a ni

201–300 ppm thleng a ni

>300 ppm a ni

CH4

75 ppm aia tlem emaw, a tlukpui emaw a ni

76–125 ppm a ni

126–200 ppm a ni

>200 ppm a ni

C₂H₄

100 ppm aia tlem emaw, a tlukpui emaw a ni

101–200 ppm inkar a ni

201–300 ppm thleng a ni

>300 ppm a ni

C₂H₂

3 ppm aia tlem emaw, a tlukpui emaw a ni

4–10 ppm a ni

11–35 ppm inkar a ni

>35 ppm a ni

CO

350 ppm aia tlem emaw, a tlukpui emaw a ni

351–570 ppm a ni

571–900 ppm a ni

>900 ppm a ni

TDCG chuan a ti a

720 ppm aia tlem emaw, a tlukpui emaw a ni

721–1,920 ppm a ni

1,921–4,630 ppm a ni

>4,630 ppm a ni

Diagnostic hnathawh dan tur:

1. Gas tinte chu IEEE C57.104 Condition levels nen khaikhin la → urgency teh rawh.

2. Duval Triangle ratios chhut → fault chi hrang hrang hriatchhuah.

3. Gas ratio pawimawh tak tak (Rogers/Doernenburg) hmangin cross-check rawh.

4. Historic trend - thlirletna rate of change a chak chho zel em?

5. Ambiguous emaw generation rate > 30%/month emaw a nih chuan sampling interval tihhniam tur.

Inquiry thawn rawh .
Inquiry thawn rawh .