DGA report ka nei a, gas pasarih concentration a awm. Engtin nge heng number te hi diagnosis ah ka chantir theih ang?
A: International-a hriat hlawh ratio method pathum hmangin gas concentration chu fault type diagnosis-ah an chantir a ni. Cross-verification atan pathum hmang vek rawh.
Thiltih dan 1: IEC 60599 / IEEE C57.104 Duval Triangle (a hman tam ber) .
|
Zone a ni |
Fault chi hrang hrang |
Gas Signature pangngai tak a ni |
|
PD a ni |
Partial discharge a ni |
H2 dominant, CH4 te tak te |
|
D1 |
Energy chhuahna hniam-(sparking) . |
C2H2 > HC zawng zawng atanga 4% a ni |
|
D2 |
Energy chhuahna sang-(arcing) . |
C2H2 + C2H4 dominant a ni |
|
T1 |
Thermal fault < 300℃a ni |
CH4 + C2H3 a thunun ber |
|
T2 |
Thermal fault 300℃–700℃ |
C2H4 > CH4 a ni |
|
T3 |
Thermal fault > 700℃a ni |
C2H4 + H2 a sang |
|
DT |
Thermal + electrical (mixed) hmanga siam a ni. |
Mixed pattern a ni |
Thiltih dan 2: IEEE C57.104 Gas awm zat tihtlem dan
|
Gas a ni |
Thil awmdan 1 (Normal) 1.1. |
Condition 2 (Fimkhur tur) 1.1. |
Thil awmdan 3 (Alert) 1.1. |
Condition 4 (Risk sang tak) 1.1. |
|
H₂ |
100 ppm aia tlem emaw, a tlukpui emaw a ni |
101–200 ppm inkar a ni |
201–300 ppm thleng a ni |
>300 ppm a ni |
|
CH4 |
75 ppm aia tlem emaw, a tlukpui emaw a ni |
76–125 ppm a ni |
126–200 ppm a ni |
>200 ppm a ni |
|
C₂H₄ |
100 ppm aia tlem emaw, a tlukpui emaw a ni |
101–200 ppm inkar a ni |
201–300 ppm thleng a ni |
>300 ppm a ni |
|
C₂H₂ |
3 ppm aia tlem emaw, a tlukpui emaw a ni |
4–10 ppm a ni |
11–35 ppm inkar a ni |
>35 ppm a ni |
|
CO |
350 ppm aia tlem emaw, a tlukpui emaw a ni |
351–570 ppm a ni |
571–900 ppm a ni |
>900 ppm a ni |
|
TDCG chuan a ti a |
720 ppm aia tlem emaw, a tlukpui emaw a ni |
721–1,920 ppm a ni |
1,921–4,630 ppm a ni |
>4,630 ppm a ni |
Diagnostic hnathawh dan tur:
1. Gas tinte chu IEEE C57.104 Condition levels nen khaikhin la → urgency teh rawh.
2. Duval Triangle ratios chhut → fault chi hrang hrang hriatchhuah.
3. Gas ratio pawimawh tak tak (Rogers/Doernenburg) hmangin cross-check rawh.
4. Historic trend - thlirletna rate of change a chak chho zel em?
5. Ambiguous emaw generation rate > 30%/month emaw a nih chuan sampling interval tihhniam tur.