Bus bar-a high voltage testing hi electrical system-a a himna leh rintlakna tur atana hmalakna pawimawh tak a ni. Hei hian bus bar-a voltage sang tak, insulation integrity, chak lohna awm thei, emaw, electrical failure emaw, hlauhawmna thlen thei chhiatna emaw a awm leh awm loh enfiah a huam a ni.
Busbar High Voltage Test-a parameter chhut ngai awmchhun chu insulation a thawk tha em tih enfiah nan leakage current a ni. Bus section CB hawn a nih chuan bus section CB closed condition nena khaikhin chuan leakage current chu a chanve a ni ang.

* HV test tih hmaa inbuatsaihna tur inbuatsaihna .

CT secondary circuit zawng zawng chu short, isolated, leh earth dik tak a ni tur a ni .

VT secondary circuit zawng zawng chu a inhawng vek tur a ni & VT racked out vek tur a ni

Test na tur bus bar chu a fai tur a ni a, leivut leh oil awm lohna tur a ni bawk .

Bus bars te grounding switch zawng zawng chu an open position ah an awm tur a ni .

Circuit-a grounding switch zawng zawng chu an open position-ah an awm tur a ni .

MV cable te chu SWGR atanga tihtawp tur a ni a, inserted cable te chu grounded & properly isolated a ni tur a ni.

SWGR room-a hnathawh zawng zawng chu tihtawp vek a ngai a, staff-te chu high voltage test chungchang hriattir vek tur a ni.

* HV test hman hmaa inbuatsaihna .

Case 1.

HV test hma leh a hnua insulation resistance test CB rack in & hawn a nih chuan .
CB rack in & hawn a nih chuan high voltage test a ni.

Case 2.

HV test hma leh hnua CB rack in closed a nih chuan insulation resistance test .
CB rack in & closed a nih chuan high voltage test a ni.

Case 3.

CB rack in & closed a nih chuan VT tan high voltage test a ni.
Case 4. CB racked in & closed a nih chuan VT tan tehna test .

* HV test hma leh a hnua insulation resistance test .

A pathumnaah hian IR atana preconditions chu a awm reng ang .
1. CB chu a rawn lut a, a rawn inhawng ta a.
2. VT chuan a rawn ti chhuak a.
3. Cable contact zawng zawng chu short leh grounded a ni.
4. Panel mamawh atanga injection pek.
5. Phase dang pahnih grounding laiin phase khatah minute 1 chhung 5 kV DC hnawih ang che.

Thil chhinchhiah:
HV test-ah chuan CB / VT status & injected voltage magnitude chu anmahni case ang zelin a danglam ang.
Bus pumpuiah panel eng pawha injection laiin aw pangngai lo a awm loh nan enfiah rawh .

* 13.8kV SWGR a voltage sang ber test a ni.
Preconditions 1000 a ni.
1. Cable contact zawng zawng chu short leh grounded a ni.
2. Panel mamawh atanga injection pek.
3. Phase dang pahnih grounding laiin phase khatah minute 1 chhung voltage inject tur a ni.
4. R- y- b phase hrang hrang case zawng zawng test vek rawh .

Case 1 a awm a.

CB chu racked in & hawn a ni.
VT chuan a rawn ti chhuak ta a.
Rated voltage ah vawi 3 inject tur a ni .

Case 2 a ni a.

CB racked in & khar a ni.
VT chuan a rawn ti chhuak ta a.
Rated voltage ah vawi 3 inject tur a ni .

Case 3.
CB racked in & khar a ni.
VT racked a ni a, 1000 a ni.
Nominal voltage ah vawi 1.5 inject .

Case 4.

CB racked in & khar a ni.
VT racked a ni a, 1000 a ni.
Inject nominal voltage & take measurements & VT circuit zawng zawng a thawk tha tawk em tih enfiah rawh.

 