Circuit breaker nei bus bar tan potential sang leh contact resistance test

 Jul 23, 2024

 Message pakhat dah la .

 

- Test tum ber:
1. Contact resistance atan chuan he test hi bus bar resistance tehna leh circuit breaker a nih hnua 1000 a nih hnua 1000 a nih hnua 1000 a resistance tehna a ni.
Site-a welding emaw install emaw avanga lo awm thei tur resistance sang lo turin site-ah dah a ni.
2. Potential sang tak atan he test hian insulations leh isolators te withstand chu voltage sang tak nen a chhe lovin teh leh test a tum a ni.

- Thil mamawh:

• Micro-Ohm meter inhnaih theihna hmanrua.
• Test kit awm thei sang tak.
- AC test theihna sang tak:
1. Megger hmanga insulation test nan insulation chu 5-kilo volt injection hmangin minute 1 chhung line 3 line leh line to ground thlengin a test thin.
2. Bus bar line leh line to ground-a high potential AC voltage hman leh service position-a CB chu energized a ni a, VTS chu racked out a ni.
3. Bus bar line-a voltage chu line leh line-a line-a voltage leh test position-a line-a voltage, protection relay-te chu energized-in VT-te chu racked out a ni.
4. High potential test kit atanga mille amperes-a passing current record chu la rawh.
5. Insulation Test Megger chuan 5-kilo Volt injection hmanga minute 1 chhung line leh line to ground thlenga insulation test turin insulation test.
6. Insulation test result chu high potential test hma leh a hnua gathers nen khaikhin rawh.
- Contact Resistance Test Connection .
1. Contact resistance device hian lead 4, current tan pahnih leh voltage tan a dang a nei a, chu chu bus bar emaw circuit breaker emaw a current injection a innghat a, chutah chuan voltage a hre a, resistance chu voltage hmangin current hmangin a chhut a (OHM’s law)
2. Bolt zawng zawng BB torquing enfiah la, factory inspection angin torque value chu confirm rawh.
3. Connect Current Leads A resistance tehna tur device inkar ah connect la, voltage leads te chu current adjust 100A injection ah connect la, contact resistance pushbutton ah i kut kha vawn la, second engemaw zat hnuah result chu a lang ang.
 

Hly-200C contact resistance tester hi Huayi Electric siam a ni a, test current chu DC 100A, 200A a ni. DC 100A-ah chuan 200A chu direct-a teh theih a ni a, contact resistance test result chu a lian zawk-screen LCD display hmangin, leh data storage, print, time settings, leh function dangte nen, leh gear dang 50A, 150A, 150A chu user thlan nan Custom test hun, a tam ber 599s, standard requirement 60s aia lian zawk; Resolution 0.01μΩ leh a nghet hle. He instrument hian current-voltage method test principle a hmang a, chu chu Four–Wire Method Testing technology a ni.