Test standard leh voltage hniam cable te hman dan tur chhui rawh .

 Aug 05, 2025

 Message pakhat dah la .

 

Heng cable te hi a him leh him loh enfiah nan. Cable siamtute tan factory acceptance tester tih theihna tur test standard leh method bik zawm a pawimawh hle. Low-voltage cables test standard leh methods te kan zir dawn a ni.

 

Test standard lian ber berte .

A hmasa ber leh pawimawh ber chu low-voltage cables atana hman tlanglawn test standards hriatthiam a pawimawh hle.

International Standards 1.1.
1. IEC 60502: 1kV atanga 30kV thlenga rated voltage nei power cable-ah hman theih a ni a, insulation thickness, conductor resistance, leh voltage test tuar thei ang chi mamawh a huam a ni.
2. IEC 60227: Polyvinyl chloride insulated cables voltage 450/750V leh a hnuai lam tan chuan conductor continuity leh insulation mechanical property te ang chi mamawh tur a tarlang a ni.

3. IEEE 400: POWER Cables atana Field Testing Guide, DC voltage test leh dielectric loss factor tehna ngaih pawimawh

 

Test dan tlangpui .

Low-voltage cable test chungchang sawi dawn chuan, a tlangpuiin hman thin key method engemaw zat a awm a.

1. Insulation do theihna test .
Thiltih dan: Ohmmeter (500V emaw 1000V range) hmangin conductor leh shielding layer inkara resistance ( 100 mω·km aia tam emaw, a tlukpui emaw) tehna hmang rawh.
Standard: GB/T 3048.5-2007 ang chuan test hun chhung hi minute 1 a ni a, environment temperature siamthat a ngai bawk.
2. Voltage test tuar thei tur .
Power frequency withstand voltage: 2.5u2 + 2kV (U 2 chu rated voltage a ni) minute 5 chhung breakdown awm lovin hnawih la (GB/T 3048.8 angin).
DC withstand voltage: Cable hlui tan a tha a, voltage chu vawi 4 atanga vawi 6 U2 a ni a, mahse insulation a upa chak thei a, fimkhur taka hman tur a ni.

3. Partial discharge (medium leh high voltage cable-a hman theih): voltage 1.5U2 hmangin, discharge zat chu 10pc aia tlem emaw, a tlukpui emaw a ni tur a ni (IEC 60885-3).

Inquiry thawn rawh .